Figure 140:
Simplified network configuration with network data, required for
settings of the fault location-measuring function
For a single-circuit line (no parallel line), the figures for mutual zero-sequence
impedance (X
0M
, R
0M
) and analog input are set at zero.
Power system specific parameter settings are not general settings but specific
setting included in the setting groups, that is, this makes it possible to change
conditions for the Fault locator with short notice by changing setting group.
The source impedance is not constant in the network. However, this has a minor
influence on the accuracy of the distance-to-fault calculation, because only the
phase angle of the distribution factor has an influence on the accuracy. The phase
angle of the distribution factor is normally very low and practically constant,
because the positive sequence line impedance, which has an angle close to 90°,
dominates it. Always set the source impedance resistance to values other than zero.
If the actual values are not known, the values that correspond to the source
impedance characteristic angle of 85° give satisfactory results.
15.8.3.1
Connection of analog currents
M13769-16 v5
Connection diagram for analog currents included IN from parallel line shown in
figure
.
Section 15
1MRK 505 393-UEN B
Monitoring
346
Line differential protection RED650 2.2 IEC
Application manual
Summary of Contents for RED650
Page 1: ...RELION 650 SERIES Line differential protection RED650 Version 2 2 Application manual ...
Page 2: ......
Page 22: ...16 ...
Page 32: ...26 ...
Page 82: ...76 ...
Page 112: ...106 ...
Page 152: ...146 ...
Page 208: ...202 ...
Page 214: ...208 ...
Page 282: ...276 ...
Page 356: ...350 ...
Page 404: ...398 ...
Page 408: ...402 ...
Page 442: ...436 ...
Page 452: ...446 ...
Page 453: ...447 ...