1MRS750527-MUM
REF 54_
125
Feeder Terminal
Technical Reference Manual, General
RTD data nominal values
The nominal values are rounded to the nearest integer (for example 2.5 = 3),
according to the RTD input signal type and the range parameters mentioned in the
Technical Reference Manual .
If a linearization curve is used for the RTD input, the nominal value of this channel
is the absolute maximum value for this curve. A store and reset is needed after
adjusting the RTD input signal type and range parameters, if new nominal values are
wanted in IEC_103.
Function blocks and available measurements
Table 9.5.-4 shows which function blocks produce measurement data mapped to the
IEC_103
class 2 measurement frames. This is how the relay configuration is
expected to be implemented. However, if signal types connected to a function block
do not match the following table, corresponding locations in the class 2 frame will
also be replaced by the actual signal types connected to the function block.
Example
If set No 11 is used, the ASDU octets will look like in the following table:
Table 9.5.-4
Function blocks and available measurements
FB name
Measurements
MECU1A
Io
MECU1B
Iob
MECU3A
IL1, IL2, IL3
MECU3B
IL1b, IL2b, IL3b
MEFR1
f
MEPE7
P, Q, PF
MEVO1A
Uo
MEVO1B
Uob
MEVO3A
U1, U2, U3, U12, U23, U31
MEVO3B
U1b, U2b, U3b, U12b, U23b, U31b
Available measurements depend on the configuration (for example
phase voltage or phase-to-phase voltage).
Table 9.5.-5
Example on ASDU octets
9
TypeId
5
VSQ=Num of data
COT
Cause of transmission
ADR
Unit address
135
Function type
140
Information Number
IL1
Data 1
IL2
Data 2
IL3
Data 3
Io
Data 4
Uo
Data 5
Summary of Contents for REF 54 Series
Page 1: ...Feeder Terminal REF 54_ Technical Reference Manual General ...
Page 2: ......
Page 12: ...12 ...
Page 20: ...20 ...
Page 102: ...102 ...
Page 126: ...126 ...
Page 130: ......
Page 131: ......