Hardware fixed filter time 1 ms.
Additional filter time can be
configured in software.
6 power outputs (channels
BO 1 to 6)
Maximum operating voltage
250 V AC/DC
Make current
8 A
Load current
6 A
Breaking capacity
1 contact 70 W, 2 contacts in
series 130 W at L/R
≤
40 ms and
10.000 operations
Operating time
8 ms
2 signal outputs (BO7 and
BO8) and 1 watchdog
output (WD)
Maximum operating voltage
250 V AC/DC
Load current
2 A
Operating time
8 ms
Optional: 1 static output on
BO7
Maximum operating voltage
250 V DC
Make current
1.5 A peak
Load current
0.7 A continuous
Operating time
1 ms
1 coil supervision circuit on
BO2
Coil OK when impedance below 10
Ω
6.4.2.
BIO module with static outputs
The technical data for the binary input and output module with static outputs are
listed in Table 6.4.2.-1. This module is full range and covers the complete voltage
range from 48 up to 265 VDC.
Table 6.4.2.-1
Technical data for the binary input and output module with
static outputs
14 inputs (BI 1-14)
Auxiliary voltage range:
48 to 265 V DC (Threshold 35 V
DC)
Hardware fixed filter time 5 ms.
Additional filter time can be
configured in software.
3 power outputs (BO1,2 and
þ7)
Operating voltage
48 to 250 V DC
Make current
64 A
Load current
16 A
Operating time
1 ms
4 power outputs (BO3 ... 6) Operating voltage
48 to 250 V DC
Make current
120 A
Load current
31 A
Operating time
1 ms
2 signal outputs (BO8,9)
and 1 watchdog output
(WD)
Operating voltage
48 to 250 V DC
Make current
1.5 A (100 ms)
R
on
1.06
Ω
R
off
40 M
Ω
Operating time
1 ms
2 coil supervision circuits on
BO1 and BO2 channels
Coil OK when impedance below 10 k
Ω
46
REF 542plus
REF 542plus
Multifunction Protection and Switchbay Control
Unit
Technical Reference Manual
1MRS755859