1. Press an arrow button to access the main menu.
2. Use the arrow buttons to select the main menu group
SETTINGS
and the wanted
group menu (for example
PROTEC. ELEMENTS
), and press
.
3. Use
or
to select the parameter to be changed and press
.
4. Use
or
to select setting group 1 or 2 (
GRP1
or
GRP2
). The active setting
group is indicated by an asterisk "
*
".
5. Enter the setting mode by pressing
and give the password if required. If the
default password 999 is still valid, no password is required.
6. The first digit of the setting value of the parameter to be edited starts to flash.
Use
and
to move the cursor and
and
to increase or decrease the
number.
7. To store a new value and return the display to the view mode, press
. If the
parameter is of a numerical kind, the display confirms the storage by flashing "
-
- -
" once on the display.
8. To exit the setting mode without storing the changes, press
once before
confirming and the display returns to the view mode.
9. Press
to return the display to the idle mode.