39
Description
Type test value
Reference
Radio frequency interference test
10 V (rms)
f = 150 kHz...80 MHz
10 V/m (rms)
f = 80...2700 MHz
10 V/m
f = 900 MHz
20 V/m (rms)
f = 80...1000 MHz
IEC 61000-4-6
IEC 60255-26, class III
IEC 61000-4-3
IEC 60255-26, class III
ENV 50204
IEC 60255-26, class III
IEEE C37.90.2-2004
Fast transient disturbance test
• All ports
4 kV
IEC 61000-4-4
IEC 60255-26
IEEE C37.90.1-2002
Surge immunity test
• Communication
• Other ports
1 kV, line-to-earth
4 kV, line-to-earth
2 kV, line-to-line
IEC 61000-4-5
IEC 60255-26
Power frequency (50 Hz) magnetic field
immunity test
• Continuous
• 1...3 s
300 A/m
300 A/m
IEC 61000-4-8
Pulse magnetic field immunity test
1000 A/m
6.4/16
μ
s
IEC 61000-4-9
Damped oscillatory magnetic field immunity test
• 2 s
• 1 MHz
100 A/m
400 transients/s
IEC 61000-4-10
Voltage dips and short interruptions
30%/10 ms
60%/100 ms
60%/1000 ms
>95%/5000 ms
IEC 61000-4-11
Power frequency immunity test
• Common mode
• Differential mode
Binary inputs only
300 V rms
150 V rms
IEC 61000-4-16
IEC 60255-26, class A
Conducted common mode disturbances
15 Hz...150 kHz
Test level 3 (10/1/10 V rms)
IEC 61000-4-16
Emission tests
• Conducted
0.15...0.50 MHz
0.5...30 MHz
• Radiated
30...230 MHz
230...1000 MHz
1…3 GHz
3…6 GHz
<79 dB (
μ
V) quasi peak
<66 dB (
μ
V) average
<73 dB (
μ
V) quasi peak
<60 dB (
μ
V) average
<40 dB (
μ
V/m) quasi peak, measured at 10 m
distance
<47 dB (
μ
V/m) quasi peak, measured at 10 m
distance
<76 dB (
μ
V/m) peak
<56 dB (
μ
V/m) average, measured at 3 m
distance
<80 dB (
μ
V/m) peak
<60 dB (
μ
V/m) average, measured at 3 m
distance
EN 55011, class A
IEC 60255-26
CISPR 11
CISPR 12
—
Table 23. Electromagnetic compatibility tests (continued)