background image

Relion

®

 630 series

Feeder Protection and Control

REF630

Product Guide

Summary of Contents for REF630

Page 1: ...Relion 630 series Feeder Protection and Control REF630 Product Guide ...

Page 2: ...ng data 63 23 Accessories 67 24 Tools 68 25 Supported ABB solutions 69 26 Terminal diagram 70 27 References 73 28 Functions codes and symbols 73 29 Document revision history 76 Disclaimer The information in this document is subject to change without notice and should not be construed as a commitment by ABB Oy ABB Oy assumes no responsibility for any errors that may appear in this document Copyrigh...

Page 3: ...nd the DNP3 communication protocol offering seamless connectivity to station automation and SCADA systems 2 Application REF630 provides main protection for overhead lines and cable feeders of distribution networks The IED fits both isolated neutral networks and networks with resistance or impedance earthed neutral Four pre defined configurations to match typical feeder protection and control requi...

Page 4: ...ar arrangement The RET630 with preconfiguration A is used for protection and control of the power transformer the REF630 with preconfiguration B protects and controls the outgoing feeder and the REF630 with preconfiguration D is used for the bus sectionalizer Feeder Protection and Control 1MRS756380 A REF630 Product version 1 0 Issued 15 09 2009 4 ABB ...

Page 5: ...guration of the LEDs and function buttons and adaptation of the default single line diagram In addition the adaptation of the preconfiguration always includes communication engineering to configure the communication according to the functionality of the IED The communication engineering is done using the communication configuration function of PCM600 If none of the offered preconfigurations fulfil...

Page 6: ...arth fault low stage 2 1 3 3 Directional earth fault high stage 1 1 1 Transient intermittent earth fault 1 1 Negative sequence overcurrent 2 2 2 2 2 Three phase thermal overload for feeder 1 1 1 1 Phase discontinuity 1 1 1 1 Three phase current inrush detection 1 1 1 1 1 Three phase overvoltage 3 3 Three phase undervoltage 3 3 Positive sequence overvoltage1 2 Positive sequence undervoltage1 2 Nega...

Page 7: ...4 4 1 10 Circuit breaker 1 1 1 1 2 Disconnector 3 3 3 8 Local remote switch interface 1 Synchrocheck1 1 Supervision and monitoring Circuit breaker condition monitoring 1 1 1 1 2 Fuse failure supervision 1 1 1 2 Current circuit supervision 1 1 1 2 Trip circuit supervision 3 3 3 3 3 Station battery supervision 1 Energy monitoring 1 Generic measured values 3 Measured value limit supervision 9 Measure...

Page 8: ...the setting values The included thermal overload protection function uses thermal models of overhead lines and cables The negative sequence overcurrent protection with two independent stages is used for phase unbalance protection In addition the IED offers phase discontinuity protection Further the IED features selective earth fault and cross country fault protection for isolated neutral and for r...

Page 9: ...IED offers voltage protection functions including three phase undervoltage and overvoltage protection with three independent stages each both with phase to phase or phase to earth measurement The IED offers overfrequency underfrequency and rate of change of frequency protection to be used in load shedding and network restoration applications In addition the IED offers three pole multi shot autorec...

Page 10: ...GUID 4460293F E493 4876 8B35 EA12DD21B7BD V1 EN Figure 3 Protection function overview of preconfiguration B Feeder Protection and Control 1MRS756380 A REF630 Product version 1 0 Issued 15 09 2009 10 ABB ...

Page 11: ... 4 Protection function overview of preconfiguration C GUID CE8BEBCD 9D9B 4FE6 A9EF AF4690339584 V1 EN Figure 5 Protection function overview of preconfiguration D Feeder Protection and Control 1MRS756380 A REF630 Product version 1 0 Issued 15 09 2009 ABB 11 ...

Page 12: ...point 7 Measurement The IED continuously measures the phase currents positive and negative sequence currents and the residual current The IED also measures phase to earth or phase to phase voltages positive and negative sequence voltages and the residual voltage In addition the IED monitors active reactive and apparent power the power factor power demand value over a user selectable pre set time f...

Page 13: ...ation can further be accessed either locally or remotely using the web browser based user interface The logging of communication events is determined by the used communication protocol and the communication engineering The communication events are automatically sent to station automation and SCADA systems once the required communication engineering has been done 10 Disturbance report The disturban...

Page 14: ...rent from a core balance current transformer or from another set of phase current transformers 16 Access control To protect the IED from unauthorized access and to maintain information integrity the IED is provided with an authentication system including user management Using the IED user management tool in the Protection and Control IED Manager PCM600 an individual password is assigned to each us...

Page 15: ...tional binary I O modules 32 27 18 Communication The IED supports the new IEC 61850 substation automation standard including horizontal GOOSE communication as well as the well established DNP3 TCP IP protocol All operational information and controls are available through these protocols Disturbance files are accessed using the IEC 61850 protocol Disturbance files are available to any Ethernet base...

Page 16: ...al time synchronization wiring IRIG B Inter Range Instrumentation Group Time Code Format B Table 5 Supported communication interface and protocol alternatives Interfaces Protocols1 Ethernet 100BASE TX RJ 45 Ethernet 100BASE FX LC IEC 61850 DNP3 Supported 1 Please refer to the Selection and ordering data chapter for more information Feeder Protection and Control 1MRS756380 A REF630 Product version ...

Page 17: ... DC Uauxvariation 85 110 of Un 85 264 V AC 80 120 of Un 38 4 150 V DC 80 120 of Un 88 300 V DC Maximum load of auxiliary voltage supply 35 W Ripple in the DC auxiliary voltage Max 15 of the DC value at frequency of 100 Hz Maximum interruption time in the auxiliary DC voltage without resetting the IED 50 ms at Uaux Power supply input must be protected by an external miniature circuit breaker For ex...

Page 18: ...Rated voltage 100 V 110 V 115 V 120 V Parametrization Voltage withstand Continuous 425 V For 10 s 450 V Burden at rated voltage 0 05 VA 1 Residual current 2 Phase currents or residual current Table 9 Binary inputs Description Value Operating range Maximum input voltage 300 V DC Rated voltage 24 250 V DC Current drain 1 6 1 8 mA Power consumption input 0 3 W Threshold voltage 15 221 V DC parametriz...

Page 19: ...h or without TCS function Description Value Rated voltage 250 V AC DC Continuous contact carry 8 A Make and carry for 3 0 s 15 A Make and carry for 0 5 s 30 A Breaking capacity when the control circuit time constant L R 40 ms at U 48 110 220 V DC 1 A 0 3 A 0 1 A Minimum contact load 100 mA at 24 V AC DC Table 12 Power output relays with TCS function Description Value Control voltage range 20 250 V...

Page 20: ...m allowed attenuation caused by connectors and cable together Table 15 X4 IRIG B interface Type Protocol Cable Screw terminal pin row header IRIG B Shielded twisted pair cable Recommended CAT 5 Belden RS 485 9841 9844 or Alpha Wire Alpha 6222 6230 Table 16 Serial rear interface Type Counter connector1 Serial port X9 Optical ST connector or optical snap in connector 1 For future use Table 17 Degree...

Page 21: ...ure 86 106 kPa Altitude up to 2000 m Transport and storage temperature range 40 85ºC Table 20 Environmental tests Description Type test value Reference Dry heat test humidity 50 96 h at 55ºC 16 h at 85ºC IEC 60068 2 2 Cold test 96 h at 25ºC 16 h at 40ºC IEC 60068 2 1 Damp heat test cyclic 6 cycles at 25 55 C humidity 93 95 IEC 60068 2 30 Storage test 96 h at 40ºC 96 h at 85ºC IEC 60068 2 48 Feeder...

Page 22: ...l 3 Radiated pulse modulated 10 V m f 900 MHz ENV 50204 IEC 60255 22 3 Radiated amplitude modulated 20 V m rms f 80 1000 MHz IEEE C37 90 2 2004 10 V m f 80 2700 MHz IEC 61000 4 3 IEC 60255 22 3 Fast transient disturbance tests IEC 61000 4 4 IEC 60255 22 4 class A Communication ports 2 kV Other ports 4 kV Surge immunity test IEC 61000 4 5 IEC 60255 22 5 level 4 3 Binary inputs 2 kV line to earth 1k...

Page 23: ...0 100 ms 60 1000 ms 70 500 ms 95 5000 ms IEC 60255 11 IEC 61000 4 11 Electromagnetic emission tests EN 55011 class A IEC 60255 25 Conducted RF emission mains terminal OK 0 15 0 50 MHz 79 dB µV quasi peak 66 dB µV average 0 5 30 MHz 73 dB µV quasi peak 60 dB µV average Radiated RF emission 30 230 MHz 40 dB µV m quasi peak measured at 10 m distance 230 1000 MHz 47 dB µV m quasi peak measured at 10 m...

Page 24: ... Isolation resistance 100 MΏ 500 V DC Protective bonding resistance IEC 60255 27 Resistance 0 1 Ώ 60 s Table 23 Mechanical tests Description Reference Requirement Vibration tests sinusoidal IEC 60068 2 6 test Fc IEC 60255 21 1 Class 1 Shock and bump test IEC 60068 2 27 test Ea shock IEC 60068 2 29 test Eb bump IEC 60255 21 2 Class 1 Seismic test IEC 60255 21 3 method A Class 1 Table 24 Product saf...

Page 25: ...ence EMC directive 2004 108 EC Standard EN 50263 2000 EN 60255 26 2007 Table 26 RoHS compliance Description Complies with RoHS directive 2002 95 EC Feeder Protection and Control 1MRS756380 A REF630 Product version 1 0 Issued 15 09 2009 ABB 25 ...

Page 26: ... Retardation time 30 ms Operate time accuracy in definite time mode 1 0 of the set value or 20 ms Operate time accuracy in inverse time mode 5 0 of the theoretical value or 20 ms 3 Suppression of harmonics RMS No suppression DFT 50dB at f n x fn where n 2 3 4 5 Peak to Peak No suppression P to P backup No suppression 1 Set Operate delay time 0 02 s Operate curve type IEC definite time Measurement ...

Page 27: ... 05 Operate delay time PHLPTOC 0 04 200 00 s 0 01 PHHPTOC 0 02 200 00 s 0 01 PHIPTOC 0 02 200 00 s 0 01 Operating curve type1 PHLPTOC Definite or inverse time Curve type 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 17 18 19 PHHPTOC Definite or inverse time Curve type 1 3 5 9 10 12 15 17 PHIPTOC Definite time 1 For further reference please refer to the Operating characteristics table Feeder Protection and C...

Page 28: ...tion time 35 ms Operate time accuracy in definite time mode 1 0 of the set value or 20 ms Operate time accuracy in inverse time mode 5 0 of the theoretical value or 20 ms3 Suppression of harmonics RMS No suppression DFT 50dB at f n x fn where n 2 3 4 5 Peak to Peak No suppression P to P backup No suppression 1 Measurement mode default depends of stage current before fault 0 0 x In fn 50 Hz fault c...

Page 29: ...ional mode DPHxPDOC 1 Non directional 2 Forward 3 Reverse Characteristic angel DPHxPDOC 179 180 deg 1 Operating curve type1 DPHLPDOC Definite or inverse time Curve type 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 17 18 19 DPHHPDOC Definite or inverse time Curve type 1 3 5 9 10 12 15 17 1 For further reference please refer to the Operating characteristics table Feeder Protection and Control 1MRS756380 A RE...

Page 30: ...30 ms Operate time accuracy in definite time mode 1 0 of the set value or 20 ms Operate time accuracy in inverse time mode 5 0 of the theoretical value or 20 ms 3 Suppression of harmonics RMS No suppression DFT 50dB at f n x fn where n 2 3 4 5 Peak to Peak No suppression 1 Operate curve type IEC definite time Measurement mode default depends on stage current before fault 0 0 x In fn 50 Hz earth fa...

Page 31: ...Operate delay time EFLPTOC 0 04 200 00 s 0 01 EFHPTOC 0 02 200 00 s 0 01 EFIPTOC 0 02 200 00 s 0 01 Operating curve type1 EFLPTOC Definite or inverse time Curve type 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 17 18 19 EFHPTOC Definite or inverse time Curve type 1 3 5 9 10 12 15 17 EFIPTOC Definite time 1 For further reference please refer to the Operating characteristics table Feeder Protection and Contr...

Page 32: ...0 ms Operate time accuracy in definite time mode 1 0 of the set value or 20 ms Operate time accuracy in inverse time mode 5 0 of the theoretical value or 20 ms 3 Suppression of harmonics RMS No suppression DFT 50dB at f n x fn where n 2 3 4 5 Peak to Peak No suppression 1 Set Operate delay time 0 06 s Operate curve type IEC definite time Measurement mode default depends on stage current before fau...

Page 33: ... 7 8 9 10 11 12 13 14 15 17 18 19 DEFHPDEF Definite or inverse time Curve type 1 3 5 15 17 Operation mode DEFLPDEF and DEFHPDEF 1 Phase angle 2 I0Sin 3 I0Cos 4 Phase angle 80 5 Phase angle 88 1 For further reference please refer to the Operating characteristics table Table 35 Transient intermittent earth fault protection INTRPTEF Characteristic Value Operation accuracy U0 criteria with transient p...

Page 34: ...accuracy At the frequency f fn 1 5 of the set value or 0 002 In Start time 1 2 IFault 2 set Start value IFault 10 set Start value Typical 23 ms 15 ms Typical 16 ms 15 ms Reset time 40 ms Reset ratio Typical 0 96 Retardation time 35 ms Operate time accuracy in definite time mode 1 0 of the set value or 20 ms Operate time accuracy in inverse time mode 5 0 of the theoretical value or 20 ms 3 Suppress...

Page 35: ... 10 11 12 13 14 15 17 18 19 1 For further reference please refer to the Operating characteristics table Table 39 Three phase thermal overload T1PTTR Characteristic Value Operation accuracy At the frequency f fn Current measurement 0 5 of the set value or 0 002 x In at currents in the range of 0 01 4 00 x In Operate time accuracy1 2 0 or 0 50 s 1 Overload current 1 2 x Operate level temperature Cur...

Page 36: ...e rise above ambient T1PTTR 0 0 200 0 deg 0 1 Time constant Time constant of the line in seconds T1PTTR 1 1000 min 1 Maximum temperature temperature level for operate T1PTTR 20 0 200 0 deg 0 1 Alarm value Temperature level for start alarm T1PTTR 20 0 150 0 deg 0 1 Reclose temperature Temperature for reset of block reclose after operate T1PTTR 20 0 150 0 deg 0 1 Initial temperature Temperature rais...

Page 37: ...SPTOC main settings Parameter Function Value Range Step Start value Current ratio setting I2 I1 PDNSPTOC 10 100 1 Operate delay time PDNSPTOC 0 100 30 000 s 0 001 Min phase current PDNSPTOC 0 05 0 30 pu 0 01 Table 43 Three phase inrush current detection INRPHAR Characteristic Value Operation accuracy At the frequency f fn Current measurement 1 5 of the set value or 0 002 x In Ratio I2f I1f measure...

Page 38: ...0 of the theoretical value or 20 ms3 Suppression of harmonics DFT 50 dB at f n fn where n 2 3 4 5 1 Start value 1 0 Un Voltage before fault 0 9 Un fn 50 Hz overvoltage in one phase to phase with nominal frequency injected from random phase angle 2 Includes the delay of the signal output contact 3 Maximum Start value 1 20 Un Start value multiples in range of 1 10 to 2 00 Table 46 Three phase overvo...

Page 39: ...0 Un Voltage before fault 1 1 Un fn 50 Hz undervoltage in one phase to phase with nominal frequency injected from random phase angle 2 Includes the delay of the signal output contact 3 Minimum Start value 0 50 Un Start value multiples in range of 0 90 to 0 20 Table 48 Three phase undervoltage protection PHPTUV main settings Parameter Function Value Range Step Start value PHPTUV 0 05 1 20 pu 0 01 T...

Page 40: ... time mode 1 0 of the set value or 20 ms Suppression of harmonics DFT 50 dB at f n x fn where n 2 3 4 5 1 Residual voltage before fault 0 0 x Un fn 50 Hz residual voltage with nominal frequency injected from random phase angle 2 Includes the delay of the signal output contact Table 50 Positive sequence overvoltage protection PSPTOV main settings Parameter Function Value Range Step Start value PSPT...

Page 41: ...ession of harmonics DFT 50 dB at f n fn where n 2 3 4 5 1 Residual voltage before fault 1 1 Un fn 50 Hz residual voltage with nominal frequency injected from random phase angle 2 Includes the delay of the signal output contact Table 52 Positive sequence undervoltage protection PSPTUV main settings Parameter Function Value Range Step Start value PSPTUV 0 010 1 200 pu 0 001 Operate delay time PSPTUV...

Page 42: ...ime mode 1 0 of the set value or 20 ms Suppression of harmonics DFT 50 dB at f n fn where n 2 3 4 5 1 Residual voltage before fault 0 0 Un fn 50 Hz residual overvoltage with nominal frequency injected from random phase angle 2 Includes the delay of the signal output contact Table 54 Negative sequence overvoltage protection NSPTOV main settings Parameter Function Value Range Step Start value NSPTOV...

Page 43: ...ntact Table 56 Residual overvoltage protection ROVPTOV main settings Parameter Function Value Range Step Start value ROVPTOV 0 010 1 000 pu 0 001 Operate delay time ROVPTOV 0 040 300 000 s 0 001 Table 57 Frequency gradient protection DAPFRC Characteristic Value Operation accuracy df dt 10 Hz s 10 mHz s Undervoltage blocking 1 5 of the set value or 0 002 Un Start time1 2 Start value 0 05 Hz s df dt...

Page 44: ...n 50 Hz 2 Includes the delay of the signal output contact Table 60 Overfrequency protection DAPTOF main settings Parameter Function Value Range Step Start value DAPTOF 35 0 64 0 Hz 0 1 Operate delay time DAPTOF 0 170 60 000 s 0 001 Table 61 Underfrequency protection DAPTUF Characteristic Value Operation accuracy At the frequency f 35 to 66 Hz 0 003 Hz Start time1 2 fFault 0 99 set Start value Typi...

Page 45: ...ression of harmonics DFT 50 dB at f n fn where n 2 3 4 5 1 Frequency before fault 1 2 fn fn 50 Hz 2 Includes the delay of the signal output contact Table 64 Load shedding LSHDPFRQ main settings Parameter Function Value Range Step Load shed mode LSHDPFRQ Freq freq AND dfdt Freq OR dfdt Restore mode LSHDPFRQ Disabled Auto Manual Start Val frequency LSHDPFRQ 35 00 60 00 Hz 0 01 Start value df dt LSHD...

Page 46: ...ep Phase voltage Meas SCEFRFLO Accurate PP without Uo Calculation Trg mode SCEFRFLO External Internal Continuous Pre fault time SCEFRFLO 0 100 300 000 s 0 001 Z Max phase load SCEFRFLO 1 00 10000 00 ohm 0 01 Ph leakage Ris SCEFRFLO 1 1000000 ohm 1 Ph capacitive React SCEFRFLO 1 1000000 ohm 1 R1 line section A SCEFRFLO 0 001 1000 000 ohm pu 0 001 X1 line section A SCEFRFLO 0 001 1000 000 ohm pu 0 0...

Page 47: ... Current value Operating phase current CCBRBRF 0 05 1 00 pu 0 05 Current value Res Operating residual current CCBRBRF 0 05 1 00 pu 0 05 CB failure mode Operating mode of function CCBRBRF 1 Current 2 Breaker status 3 Both CB fail trip mode CCBRBRF 1 Off 2 Without check 3 Current check Retrip time CCBRBRF 0 00 60 00 s 0 01 CB failure delay CCBRBRF 0 00 60 00 s 0 01 CB fault delay CCBRBRF 0 00 60 00 ...

Page 48: ...le 2 Start time 1 2 SIR3 0 1 60 Typical 50 ms 15 ms Transient overreach SIR 0 1 60 6 Reset time 50 ms Reset ratio Typical 0 96 Operate time accuracy in definite time mode 1 0 of the set value or 20 ms 1 Includes the delay of the signal output contact 2 Relates to start signals of the Zone Z1 Zone ZAR2 3 SIR Source impedance ratio Feeder Protection and Control 1MRS756380 A REF630 Product version 1 ...

Page 49: ...P V Ph Sel GFC DSTPDIS 0 10 1 00 pu 0 01 Z Chr Mod Ph Sel GFC DSTPDIS Quadrilateral Mho circular Load Dsr mode GFC DSTPDIS Off On X Gnd Fwd reach GFC DSTPDIS 0 01 3000 00 ohm 0 01 X Gnd Rv reach GFC DSTPDIS 0 01 3000 00 ohm 0 01 Ris Gnd Rch GFC DSTPDIS 0 01 500 00 ohm 0 01 X PP Fwd reach GFC DSTPDIS 0 01 3000 00 ohm 0 01 X PP Rv reach GFC DSTPDIS 0 01 3000 00 ohm 0 01 Resistive PP Rch GFC DSTPDIS ...

Page 50: ...ltage XCF GFC DSTPDIS 0 10 1 00 pu 0 01 Cross country Dl GFC DSTPDIS 0 00 10 00 s 0 01 Impedance mode Zn DSTPDIS Rectangular Polar Impedance Chr Gnd Zn DSTPDIS Quadrilateral Mho circular Mho dir line Offset dir line Bullet combi Impedance Chr PP Zn DSTPDIS Quadrilateral Mho circular Mho dir line Offset dir line Bullet combi Max phase angle zone DSTPDIS 0 45 deg 1 Min phase angle zone DSTPDIS 90 13...

Page 51: ... 100 00 ohm 0 01 R0 zone 1 DSTPDIS 0 01 3000 00 ohm 0 01 X0 zone 1 DSTPDIS 0 01 3000 00 ohm 0 01 Factor K0 zone 1 DSTPDIS 0 0 4 0 0 1 Factor K0 angle Zn1 DSTPDIS 135 135 deg 1 Min Ris Gnd Rch Zn1 DSTPDIS 0 01 500 00 ohm 0 01 Max Ris Gnd Rch Zn1 DSTPDIS 0 01 500 00 ohm 0 01 Gnd operate Dl Zn1 DSTPDIS 0 030 60 000 s 0 001 Table 71 Switch onto fault function CVRSOF Characteristic Value Operation accu...

Page 52: ...d release on time DSTPLAL 0 000 60 000 s 0 001 Load release off Tm DSTPLAL 0 000 60 000 s 0 001 Loss of load Op DSTPLAL Disabled Enabled Zone extension DSTPLAL Disabled Enabled Table 74 Communication logic for residual overcurrent RESCPSCH Characteristic Value Operate time accuracy 1 0 of the set value or 20 ms Table 75 Communication logic for residual overcurrent RESCPSCH main settings Parameter ...

Page 53: ... accuracy At the frequency f fn 1 5 of the set value or 0 002 Un Operate time accuracy 1 0 of the set value or 20 ms Suppression of harmonics DFT 50 dB at f n x fn where n 2 3 4 5 Table 79 Current reversal and WEI logic CRWPSCH main settings Parameter Function Value Range Step Reversal mode CRWPSCH Off On Wei mode CRWPSCH Off Echo Echo Trip PhV level for Wei CRWPSCH 0 10 0 90 pu 0 01 PPV level for...

Page 54: ...l and WEI logic for residual overcurrent RCRWPSCH main settings Parameter Function Value Range Step Reversal mode RCRWPSCH Off On Wei mode RCRWPSCH Off Echo Echo Trip Residual voltage Val RCRWPSCH 0 05 0 70 pu 0 01 Reversal time RCRWPSCH 0 000 60 000 s 0 001 Reversal reset time RCRWPSCH 0 000 60 000 s 0 001 Wei Crd time RCRWPSCH 0 000 60 000 s 0 001 Feeder Protection and Control 1MRS756380 A REF63...

Page 55: ... 14 IEC L T inv 15 IEC Def Time 17 Programmable 18 RI type 19 RD type Operating curve type voltage protection 5 ANSI Def Time 15 IEC Def Time 17 Inv Curve A 18 Inv Curve B 19 Inv Curve C 20 Programmable 21 Inv Curve A 22 Inv Curve B 23 Programmable Control functions Table 83 Autoreclosure DARREC Characteristic Value Operate time accuracy 1 0 of the set value or 20 ms Feeder Protection and Control ...

Page 56: ...alue Operation accuracy At the frequency f fn 0 5 or 0 002 x In at currents in the range of 0 01 4 00 x In Suppression of harmonics DFT 50dB at f n x fn where n 2 3 4 5 RMS No suppression Table 86 Three phase voltage measurement VPHMMXU Characteristic Value Operation accuracy At the frequency f fn 0 5 or 0 002 x Un at voltages in the range of 0 01 1 15 Un Suppression of harmonics DFT 50dB at f n f...

Page 57: ...aracteristic Value Operation accuracy At the frequency f fn 0 5 or 0 002 x In at currents in the range of 0 01 4 00 x In Suppression of harmonics DFT 50dB at f n x fn where n 2 3 4 5 RMS No suppression Table 89 Residual voltage measurement RESVMMXU Characteristic Value Operation accuracy At the frequency f fn 0 5 or 0 002 Un Suppression of harmonics DFT 50dB at f n fn where n 2 3 4 5 RMS No suppre...

Page 58: ... n x fn where n 2 3 4 5 Table 91 Current sequence components CSMSQI Characteristic Value Operation accuracy At the frequency f fn 1 0 or 0 002 x In at currents in the range of 0 01 4 00 x In Suppression of harmonics DFT 50dB at f n x fn where n 2 3 4 5 Table 92 Voltage sequence components VSMSQI Characteristic Value Operation accuracy At the frequency f fn 1 0 or 0 002 x Un At voltages in range of...

Page 59: ... Value Current measuring accuracy At the frequency f fn 1 5 or 0 002 In at currents in the range of 0 1 10 In 5 0 at currents in the range of 10 40 In Operate time accuracy 1 0 of the set value or 20 ms Traveling time measurement 10 ms Table 95 Current circuit supervision CCRDIF Characteristic Value Operate time1 30 ms 1 Including the delay of the output contact Table 96 Current circuit supervisio...

Page 60: ... 25 ms 15 ms Delta function ΔU 1 1 x set Voltage change rate Typical 35 ms 15 ms ΔU 2 0 x set Voltage change rate Typical 28 ms 15 ms 1 Includes the delay of the signal output contact fn 50 Hz fault voltage with nominal frequency injected from random phase angle Table 98 Station battery supervision SPVNZBAT Characteristic Value Operation accuracy 1 0 of the set value Operate time accuracy 1 0 of t...

Page 61: ...5CFD3446 A92F 4A5F B60D 90025DCFDC61 V2 EN Figure 6 Local user interface 21 Mounting methods By means of appropriate mounting accessories the standard IED case for the 630 series IEDs can be flush mounted semi flush mounted or wall mounted If the IED is delivered with a detached local HMI the HMI can be mounted on the door and the IED case in the low voltage compartment of the switchgear Further t...

Page 62: ...677 E3CF75DB256F V1 EN Figure 7 Flush mounting GUID AF1BEC0B A9DC 4E9B 9C89 98F28B1C81DB V1 EN Figure 8 Semi flush mounting GUID 945D3C86 A432 4C1F 927A A208E0C1F5F6 V1 EN Figure 9 Wall mounting Feeder Protection and Control 1MRS756380 A REF630 Product version 1 0 Issued 15 09 2009 62 ABB ...

Page 63: ... The order number consists of a string of codes generated from the hardware and software modules of the IED Use the ordering key information in tables to generate the order number when ordering protection and control IEDs S B F BABAC B B B ZAZ NAXA DESCRIPTION 1 IED 630 series IED 4U half 19 housing S 2 Standard IEC B 3 Main application Feeder protection and control F GUID 3C2FC288 F60C 4ED6 BA44 ...

Page 64: ...ailable analog inputs options 5 6 Available binary in puts output options 7 8 A AB 4 I I0 1 5A 1 I I0 0 1 0 5A 4 U AB 23 BI 18 BO or AC 32 BI 27 BO B AB 4 I I0 1 5A 1 I I0 0 1 0 5A 4U AB 23 BI 18 BO or AC 32 BI 27 BO C 1 AB 4 I I0 1 5A 1 I I0 0 1 0 5A 4 U AB 23 BI 18 BO or AC 32 BI 27 BO D AB 4 I I0 1 5A 1 I I0 0 1 0 5A 4 U AB 23 BI 18 BO or AC 32 BI 27 BO N AA 4 I I0 1 5A 5 U or AB 4 I I0 1 5A 1 ...

Page 65: ...connector B 10 Communication Ethernet Ethernet 100BaseFX LC A Ethernet 100BaseTX RJ 45 B 11 Communication protocol IEC 61850 A IEC 61850 and DNP3 TCP IP B 1 For future use GUID E305C090 B0F2 4140 8EF0 F71776D0BCB2 V1 EN Feeder Protection and Control 1MRS756380 A REF630 Product version 1 0 Issued 15 09 2009 ABB 65 ...

Page 66: ...protection fault locator and synchro check 6 F All options 7 Z None N 15 Option 2 Fault locator A Synchro check B Phase sequence voltage functions C Distance protection D None N 16 Power supply 48 125 V DC A 110 250 V DC 100 240 V AC B 17 Vacant digit Vacant X 18 Version Version 1 0 A 1 Available options for digit 15 restricted to N C or D 2 Available options for digit 15 restricted to N B or D 3 ...

Page 67: ...o the front for one 4U half 19 housing IED 1KHL400039R0001 19 rack mounting kit for one 4U half 19 housing IED 1KHL400236R0001 19 rack mounting kit for two 4U half 19 housing IEDs 1KHL400237R0001 Overhead ceiling mounting kit with cable space for one 4U half 19 housing IED 1KHL400038P0001 Table 100 Test switch mounting accessories Item Order number 19 rack mounting kit for one RTXP8 test switch th...

Page 68: ... used the IED can be accessed either locally or remotely using a web browser IE 7 0 or later For security reasons the web browser based user interface is disabled by default The interface can be enabled with the PCM600 tool or from the front panel user interface The functionality of the interface is by default limited to read only but can be configured to enable read and write access by means of P...

Page 69: ...stribution in utility and industrial power systems To facilitate and streamline the system engineering ABB s IEDs are supplied with Connectivity Packages containing a compilation of software and IED specific information including single line diagram templates a full IED data model including event and parameter lists By utilizing the Connectivity Packages the IEDs can be readily configured via the ...

Page 70: ...ar bay solutions To enhance personnel safety the web HMI also enables remote access to substation devices and processes Furthermore COM600 can be used as a local data warehouse for technical documentation of the substation and for network data collected by the IEDs The collected network data facilitates extensive reporting and analyzing of network fault situations using the data historian and even...

Page 71: ...26 Terminal diagram GUID D5305298 BC76 4649 812A 9434571FE7BB V2 EN Figure 11 REF630 terminal diagram Feeder Protection and Control 1MRS756380 A REF630 Product version 1 0 Issued 15 09 2009 ABB 71 ...

Page 72: ... 3 4 5 PO3 PO2 PO1 SO1 SO2 SO3 SO6 1 2 4 5 7 8 9 10 11 13 14 15 17 18 3 6 12 16 SO5 13 14 15 SO4 SO5 BI2 BI3 BI4 BI5 BI6 BI7 BI8 BI9 BI8 BI9 BI6 BI7 BI4 BI5 BI2 BI3 BI1 BI1 GUID 6DCDED52 BE0B 4AC9 B909 2961E13EE234 V1 EN Figure 12 Terminal diagram option for REF630 Feeder Protection and Control 1MRS756380 A REF630 Product version 1 0 Issued 15 09 2009 72 ABB ...

Page 73: ...ea on the right hand side of the web page contains the latest product documentation such as technical reference manual installation manual operators manual etc The selection tool on the web page helps you find the documents by the document category and language The Features and Application tabs contain product related information in a compact format Feeder Protection and Control 1MRS756380 A REF63...

Page 74: ...onal earth fault instantaneous stage EFIPTOC I0 50N 51N Directional earth fault low stage DEFLPDEF I0 67N 1 Directional earth fault high stage DEFHPDEF I0 67N 2 Transient intermittent earth fault INTRPTEF I0 IEF 67NIEF Negative sequence overcurrent NSPTOC I2 46 Three phase thermal overload for feeder T1PTTR 3Ith F 49F Three phase overvoltage PHPTOV 3U 59 Three phase undervoltage PHPTUV 3U 27 Posit...

Page 75: ...n logic DSOCPSCH CL 85 Current reversal and WEI logic CRWPSCH CLCRW 85CRW Current reversal and WEI logic for residual overcurrent RCRWPSCH CLCRWN 85NCRW Control Bay control QCCBAY CBAY CBAY Interlocking interface SCILO 3 3 Circuit breaker disconnector control GNRLCSWI I O CB DC I O CB DC Circuit breaker DAXCBR I O CB I O CB Disconnector DAXSWI I O DC I O DC Local remote switch interface LOCREM R L...

Page 76: ...I1 I2 I1 I2 Sequence voltage VSMSQI U1 U2 V1 V2 Power monitoring with P Q S power factor frequency PWRMMXU PQf PQf Metering Pulse counter for energy metering PCGGIO Disturbance recorder function Disturbance recorder DRRDRE DREC DREC Analog channels 1 10 samples A1RADR ACH1 ACH1 Analog channel 11 20 samples A2RADR ACH2 ACH2 Analog channel 21 30 samples A3RADR ACH3 ACH3 Analog channel 31 40 calc val...

Page 77: ...29 Document revision history Document revision date Product version History A 15 09 2009 1 0 First release Feeder Protection and Control 1MRS756380 A REF630 Product version 1 0 Issued 15 09 2009 ABB 77 ...

Page 78: ...78 ...

Page 79: ......

Page 80: ...Contact us ABB Oy Distribution Automation P O Box 699 FI 65101 VAASA Finland Phone 358 10 22 11 Fax 358 10 22 41094 www abb com substationautomation 1MRS756380 A Copyright 2009 ABB All rights reserved ...

Reviews: