6.1.4
Technical data
Table 30:
T2WPDIF, T3WPDIF technical data
Function
Range or value
Accuracy
Operating characteristic
Adaptable
± 1.0% of Ir for I < Ir
± 1.0% of I for I > Ir
Reset ratio
>94%
-
Unrestrained differential current limit
(1.00-50.00)x
IBase on
high voltage winding
± 1.0% of set value
Base sensitivity function
(0.05 - 0.60) x
IBase
± 1.0% of Ir
Minimum negative sequence current
(0.02 - 0.20) x
IBase
± 1.0% of Ir
Operate angle, negative sequence
(30.0 - 90.0) degrees
± 1.0 degrees
Second harmonic blocking
(5.0-100.0)% of
fundamental differential
current
± 2.0% of applied harmonic
magnitude
Fifth harmonic blocking
(5.0-100.0)% of
fundamental differential
current
± 12.0% of applied harmonic
magnitude
Connection type for each of the windings
Y or D
-
Phase displacement between high voltage
winding, W1 and each of the windings, W2
and W3. Hour notation
0–11
-
Operate time, restrained function
25 ms typically at 0 to 5
x set level
-
Reset time, restrained function
25 ms typically at 5 to 0
x set level
-
Operate time, unrestrained function
20 ms typically at 0 to 5
x set level
-
Reset time, unrestrained function
25 ms typically at 5 to 0
x set level
-
6.2
Restricted earth-fault protection, low impedance
REFPDIF
6.2.1
Identification
Function description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Restricted earth-fault protection, low
impedance
REFPDIF
IdN/I
SYMBOL-AA V1 EN
87N
1MRK 502 048-UEN A
Section 6
Differential protection
109
Technical manual
Summary of Contents for REG650 ANSI
Page 1: ...Relion 650 series Generator protection REG650 Technical manual ...
Page 2: ......
Page 36: ...30 ...
Page 42: ...36 ...
Page 50: ...44 ...
Page 64: ...58 ...
Page 86: ...80 ...
Page 262: ...256 ...
Page 300: ...294 ...
Page 438: ...432 ...
Page 476: ...470 ...
Page 592: ...586 ...
Page 664: ...658 ...
Page 678: ...672 ...
Page 726: ...720 ...
Page 727: ...721 ...