R
jx
Mho, zone3
Mho, zone2
Mho, zone1
IEC09000172_1_en.vsd
IEC09000172 V1 EN
Figure 67:
Mho, offset mho characteristic
Zone 3 can be equipped with a load encroachment function which cuts off a section of
the characteristic when enabled. The function is activated by setting the parameter
LoadEnchModZ3
to
On
. Enabling of the load encroachment function increases the
possibility to detect high resistive faults without interfering with the load impedance.
The algorithm for the load encroachment is located in the Load encroachment
(LEPDIS) function, where the relevant settings can be found. Information about load
encroachment from LEPDIS function to zone measurement is sent via the input signal
LDCND in binary format.
7.2.6.3
Basic operation characteristics
Each impedance zone can be enabled and disabled by setting
OpModeZx
(where
x
is
1-3 depending on selected zone).
The zone reach for phase-to-phase fault is set individually in polar coordinates. The
impedance is set by the parameter
ZxFwd
and
ZxRev
and the corresponding arguments
by the parameter
ImpedanceAng
. The setting
ImpedanceAng
is common for all three
zones.
Section 7
1MRK 502 048-UEN A
Impedance protection
150
Technical manual
Summary of Contents for REG650 ANSI
Page 1: ...Relion 650 series Generator protection REG650 Technical manual ...
Page 2: ......
Page 36: ...30 ...
Page 42: ...36 ...
Page 50: ...44 ...
Page 64: ...58 ...
Page 86: ...80 ...
Page 262: ...256 ...
Page 300: ...294 ...
Page 438: ...432 ...
Page 476: ...470 ...
Page 592: ...586 ...
Page 664: ...658 ...
Page 678: ...672 ...
Page 726: ...720 ...
Page 727: ...721 ...