R
X
Underexcitation Protection
Restrain area
DirAngle
XoffsetDirLine
Z (apparent impedance)
en06000457.vsd
IEC06000457 V1 EN
Figure 73:
Impedance constructed as XoffsetDirLine in LEXPDIS protection
LEXPDIS function is schematically described in figure
en06000458-2.vsd
Apparent
impedance
calculation
Positive
sequence
current
phasor
Z
Z in
Z1 char.
Z in
Z2 char.
Dir.
Restrain
³1
Dir.Restrain ON
&
&
startZ1
startZ2
t
t
TripZ1
TripZ2
tZ1
tZ2
Positive
sequence
voltage
phasor
IEC06000458 V3 EN
Figure 74:
Simplified logic diagram of LEXPDIS protection
1MRK 502 048-UEN A
Section 7
Impedance protection
159
Technical manual