Table 87:
OC4PTOC Non group settings (basic)
Name
Values (Range)
Unit
Step
Default
Description
GlobalBaseSel
1 - 6
-
1
1
Selection of one of the Global Base Value
groups
MeasType
DFT
RMS
-
-
DFT
Selection between DFT and RMS
measurement
8.1.6
Monitored data
Table 88:
OC4PTOC Monitored data
Name
Type
Values (Range)
Unit
Description
DIRL1
INTEGER
1=Forward
2=Reverse
0=No direction
-
Direction for phase L1
DIRL2
INTEGER
1=Forward
2=Reverse
0=No direction
-
Direction for phase L2
DIRL3
INTEGER
1=Forward
2=Reverse
0=No direction
-
Direction for phase L3
IL1
REAL
-
A
Current in phase L1
IL2
REAL
-
A
Current in phase L2
IL3
REAL
-
A
Current in phase L3
8.1.7
Operation principle
The Four step phase overcurrent protection 3-phase output OC4PTOC is divided into
four different sub-functions, one for each step. For each step
x
, where x is step 1, 2,
3 and 4, an operation mode is set by
DirModex
:
Off
/
Non-directional
/
Forward
/
Reverse
.
The protection design can be divided in four parts:
•
The direction element
•
The harmonic Restraint Blocking function
•
The four step over current function
•
The mode selection
If VT inputs are not available or not connected, setting parameter
DirModex
shall be left to default value,
Non-directional
.
1MRK 502 048-UEN A
Section 8
Current protection
181
Technical manual
Summary of Contents for REG650 ANSI
Page 1: ...Relion 650 series Generator protection REG650 Technical manual ...
Page 2: ......
Page 36: ...30 ...
Page 42: ...36 ...
Page 50: ...44 ...
Page 64: ...58 ...
Page 86: ...80 ...
Page 262: ...256 ...
Page 300: ...294 ...
Page 438: ...432 ...
Page 476: ...470 ...
Page 592: ...586 ...
Page 664: ...658 ...
Page 678: ...672 ...
Page 726: ...720 ...
Page 727: ...721 ...