8.2.2
Functionality
The four step residual overcurrent protection, zero or negative sequence direction
(EF4PTOC) has a settable inverse or definite time delay independent for step 1 and 4
separately. Step 2 and 3 are always definite time delayed.
All IEC and ANSI inverse time characteristics are available.
EF4PTOC can be set directional or non-directional independently for each of the
steps.
The directional part of the function can be set to operate on following combinations:
•
Directional current (I3PDir) versus Polarizing voltage (U3PPol)
•
Directional current (I3PDir) versus Polarizing current (I3PPol)
•
Directional current (I3PDir) versus Dual polarizing (UPol+ZPol x IPol) where
ZPol = RPol + jXPol
IDir, UPol and IPol can be independently selected to be either zero sequence or
negative sequence.
Other setting combinations are possible, but not recommended.
Second harmonic blocking level can be set for the function and can be used to block
each step individually.
8.2.3
Function block
IEC08000004-2-en.vsd
EF4PTOC
I3P*
U3P*
I3PPOL*
I3PDIR*
BLOCK
BLKST1
BLKST2
BLKST3
BLKST4
TRIP
TR1
TR2
TR3
TR4
START
ST1
ST2
ST3
ST4
STFW
STRV
2NDHARMD
IEC08000004 V2 EN
Figure 92:
EF4PTOC function block
1MRK 502 048-UEN A
Section 8
Current protection
187
Technical manual
Summary of Contents for REG650 ANSI
Page 1: ...Relion 650 series Generator protection REG650 Technical manual ...
Page 2: ......
Page 36: ...30 ...
Page 42: ...36 ...
Page 50: ...44 ...
Page 64: ...58 ...
Page 86: ...80 ...
Page 262: ...256 ...
Page 300: ...294 ...
Page 438: ...432 ...
Page 476: ...470 ...
Page 592: ...586 ...
Page 664: ...658 ...
Page 678: ...672 ...
Page 726: ...720 ...
Page 727: ...721 ...