Name
Values (Range)
Unit
Step
Default
Description
IMin4
1 - 10000
%IB
1
17
Minimum operate current for step 4 in % of
IBase
t4Min
0.000 - 60.000
s
0.001
0.000
Minimum operate time in inverse curves
step 4
HarmRestrain4
Off
On
-
-
On
Enable block of step 4 from harmonic
restrain
Table 93:
EF4PTOC Non group settings (basic)
Name
Values (Range)
Unit
Step
Default
Description
GlobalBaseSel
1 - 6
-
1
1
Selection of one of the Global Base Value
groups
SeqTypeUPol
ZeroSeq
NegSeq
-
-
ZeroSeq
Choice of measurand for polarizing
voltage
SeqTypeIPol
ZeroSeq
NegSeq
-
-
ZeroSeq
Choice of measurand for polarizing
current
SeqTypeIDir
ZeroSeq
NegSeq
-
-
ZeroSeq
Choice of measurand for directional
current
8.2.6
Monitored data
Table 94:
EF4PTOC Monitored data
Name
Type
Values (Range)
Unit
Description
STDIR
INTEGER
3=Both
1=Forward
2=Reverse
0=No direction
-
Fault direction coded as
integer
IOp
REAL
-
A
Operating current level
UPol
REAL
-
kV
Polarizing voltage level
IPol
REAL
-
A
Polarizing current level
UPOLIANG
REAL
-
deg
Angle between polarizing
voltage and operating
current
IPOLIANG
REAL
-
deg
Angle between polarizing
current and operating
current
IOPDIR
REAL
-
A
Amplitude of the
directional operating
quantity
8.2.7
Operation principle
Four step residual overcurrent protection, zero or negative sequence direction
EF4PTOC function has the following four “Analog Inputs” on its function block in the
configuration tool:
1MRK 502 048-UEN A
Section 8
Current protection
191
Technical manual
Summary of Contents for REG650 ANSI
Page 1: ...Relion 650 series Generator protection REG650 Technical manual ...
Page 2: ......
Page 36: ...30 ...
Page 42: ...36 ...
Page 50: ...44 ...
Page 64: ...58 ...
Page 86: ...80 ...
Page 262: ...256 ...
Page 300: ...294 ...
Page 438: ...432 ...
Page 476: ...470 ...
Page 592: ...586 ...
Page 664: ...658 ...
Page 678: ...672 ...
Page 726: ...720 ...
Page 727: ...721 ...