STRV
0.6 * I>DIR
STFW
-RCA -85 deg
40% of
I>DIR
I>DIR
RCA
65 deg
U = -U
pol 2
I = I
op 2
RCA +85 deg
RCA -85 deg
Characteristic
for STRV
Operating area
Operating area
Characteristic
for STFW
Characteristic for reverse
release of measuring steps
Characteristic for forward
release of measuring steps
-RCA +85 deg
IEC11000269-2-en.ai
IEC11000269 V2 EN
Figure 96:
Operating characteristic for earth-fault directional element using the
negative sequence components
Two relevant setting parameters for directional supervision element are:
•
Directional element will be internally enabled to operate as soon as Iop is bigger
than 40% of
I>Dir
and directional condition is fulfilled in set direction.
•
Relay characteristic angle
AngleRCA
, which defines the position of forward and
reverse areas in the operating characteristic.
Directional comparison step, built-in within directional supervision element, will set
EF4PTOC function output binary signals:
1. STFW=1 when operating quantity magnitude Iop x cos(φ -
AngleRCA
) is bigger
than setting parameter
I>Dir
and directional supervision element detects fault in
forward direction.
2. STRV=1 when operating quantity magnitude Iop x cos(φ -
AngleRCA
) is bigger
than 60% of setting parameter
I>Dir
and directional supervision element detects
fault in reverse direction.
Section 8
1MRK 502 048-UEN A
Current protection
200
Technical manual
Summary of Contents for REG650 ANSI
Page 1: ...Relion 650 series Generator protection REG650 Technical manual ...
Page 2: ......
Page 36: ...30 ...
Page 42: ...36 ...
Page 50: ...44 ...
Page 64: ...58 ...
Page 86: ...80 ...
Page 262: ...256 ...
Page 300: ...294 ...
Page 438: ...432 ...
Page 476: ...470 ...
Page 592: ...586 ...
Page 664: ...658 ...
Page 678: ...672 ...
Page 726: ...720 ...
Page 727: ...721 ...