Name
Values (Range)
Unit
Step
Default
Description
kIN
0.00 - 2.00
-
0.01
1.00
IDMT time multiplier for non-directional
residual overcurrent
OpUN>
Off
On
-
-
Off
Operation of non-directional residual
overvoltage
UN>
1.00 - 300.00
%UB
0.01
20.00
Set level for non-dir residual voltage, % of
UBase
tUN
0.000 - 60.000
s
0.001
0.100
Time delay for non-directional residual
overvoltage
INRel>
0.25 - 200.00
%IB
0.01
1.00
Residual release current for all directional
modes, in % of IBase
UNRel>
1.00 - 300.00
%UB
0.01
3.00
Residual release volt for all dir modes, %
of UBase
Table 99:
SDEPSDE Non group settings (basic)
Name
Values (Range)
Unit
Step
Default
Description
GlobalBaseSel
1 - 6
-
1
1
Selection of one of the Global Base Value
groups
8.3.6
Monitored data
Table 100:
SDEPSDE Monitored data
Name
Type
Values (Range)
Unit
Description
INCOSPHI
REAL
-
A
Mag of residual current
along polarizing qty
3I0cos(Fi-RCA)
IN
REAL
-
A
Measured magnitude of
the residual current 3I0
UN
REAL
-
kV
Measured magnitude of
the residual voltage 3U0
SN
REAL
-
MVA
Measured magnitude of
residual power
3I03U0cos(Fi-RCA)
ANG FI-RCA
REAL
-
deg
Angle between 3U0 and
3I0 minus RCA (Fi-RCA)
8.3.7
Operation principle
8.3.7.1
Function inputs
The function is using phasors of the residual current and voltage. Group signals I3P
and U3P containing phasors of residual current and voltage is taken from pre-
processor blocks.
The sensitive directional earth fault protection has the following sub-functions
included:
Section 8
1MRK 502 048-UEN A
Current protection
206
Technical manual
Summary of Contents for REG650 ANSI
Page 1: ...Relion 650 series Generator protection REG650 Technical manual ...
Page 2: ......
Page 36: ...30 ...
Page 42: ...36 ...
Page 50: ...44 ...
Page 64: ...58 ...
Page 86: ...80 ...
Page 262: ...256 ...
Page 300: ...294 ...
Page 438: ...432 ...
Page 476: ...470 ...
Page 592: ...586 ...
Page 664: ...658 ...
Page 678: ...672 ...
Page 726: ...720 ...
Page 727: ...721 ...