For trip, both the residual current 3I
0
·cos φ and the release voltage 3U
0
, must be larger
than the set levels:
INCosPhi>
and
UNRel>
.
When the function is activated binary output signals START and STDIRIN are
activated. If the output signals are active after the set delay
tDef
the binary output
signals TRIP and TRDIRIN are activated. The trip from this sub-function has definite
time delay.
There is a possibility to increase the operate level for currents where the angle φ is
larger than a set value as shown in figure
. This is equivalent to blocking of the
function if φ >
ROADir
. This option is used to handle angle error for the instrument
transformers.
Operate area
ROADir
IEC06000650_2_en.vsd
=
o
0
RCADir
0
3
I
j
0
3
×
j
I cos
-
=
0
3
ref
U
U
IEC06000650 V2 EN
Figure 102:
Characteristic with ROADir restriction
The function indicates forward/reverse direction to the fault. Reverse direction is
defined as 3I
0
·cos (φ + 180°) ≥ the set value.
It is also possible to tilt the characteristic to compensate for current transformer angle
error with a setting
RCAComp
as shown in the figure
Section 8
1MRK 502 048-UEN A
Current protection
208
Technical manual
Summary of Contents for REG650 ANSI
Page 1: ...Relion 650 series Generator protection REG650 Technical manual ...
Page 2: ......
Page 36: ...30 ...
Page 42: ...36 ...
Page 50: ...44 ...
Page 64: ...58 ...
Page 86: ...80 ...
Page 262: ...256 ...
Page 300: ...294 ...
Page 438: ...432 ...
Page 476: ...470 ...
Page 592: ...586 ...
Page 664: ...658 ...
Page 678: ...672 ...
Page 726: ...720 ...
Page 727: ...721 ...