Name
Type
Description
START1
BOOLEAN
Start signal from stage 1
START2
BOOLEAN
Start signal from stage 2
P
REAL
Active Power
PPERCENT
REAL
Active power in % of calculated power base value
Q
REAL
Reactive power
QPERCENT
REAL
Reactive power in % of calculated power base
value
8.7.2.4
Settings
Table 123:
GOPPDOP Group settings (basic)
Name
Values (Range)
Unit
Step
Default
Description
Operation
Off
On
-
-
Off
Operation Off / On
OpMode1
Off
OverPower
-
-
OverPower
Operation mode 1
Power1
0.0 - 500.0
%
0.1
1.0
Power setting for stage 1 in % of
calculated power base value
Angle1
-180.0 - 180.0
Deg
0.1
0.0
Characteristic angle for stage 1
TripDelay1
0.010 - 6000.000
s
0.001
1.000
Trip delay for stage 1
OpMode2
Off
OverPower
-
-
OverPower
Operation mode 2
Power2
0.0 - 500.0
%
0.1
1.0
Power setting for stage 2 in % of
calculated power base value
Angle2
-180.0 - 180.0
Deg
0.1
0.0
Characteristic angle for stage 2
TripDelay2
0.010 - 6000.000
s
0.001
1.000
Trip delay for stage 2
Table 124:
GOPPDOP Group settings (advanced)
Name
Values (Range)
Unit
Step
Default
Description
k
0.00 - 0.99
-
0.01
0.00
Low pass filter coefficient for power
measurement, U and I
Table 125:
GOPPDOP Non group settings (basic)
Name
Values (Range)
Unit
Step
Default
Description
GlobalBaseSel
1 - 6
-
1
1
Selection of one of the Global Base Value
groups
Mode
L1, L2, L3
Arone
Pos Seq
L1L2
L2L3
L3L1
L1
L2
L3
-
-
Pos Seq
Mode of measurement for current and
voltage
1MRK 502 048-UEN A
Section 8
Current protection
233
Technical manual
Summary of Contents for REG650 ANSI
Page 1: ...Relion 650 series Generator protection REG650 Technical manual ...
Page 2: ......
Page 36: ...30 ...
Page 42: ...36 ...
Page 50: ...44 ...
Page 64: ...58 ...
Page 86: ...80 ...
Page 262: ...256 ...
Page 300: ...294 ...
Page 438: ...432 ...
Page 476: ...470 ...
Page 592: ...586 ...
Page 664: ...658 ...
Page 678: ...672 ...
Page 726: ...720 ...
Page 727: ...721 ...