9.1.4
Signals
Table 154:
UV2PTUV Input signals
Name
Type
Default
Description
U3P
GROUP
SIGNAL
-
Three phase group signal for voltage inputs
BLOCK
BOOLEAN
0
Block of function
BLKST1
BOOLEAN
0
Block of step 1
BLKST2
BOOLEAN
0
Block of step 2
Table 155:
UV2PTUV Output signals
Name
Type
Description
TRIP
BOOLEAN
General trip signal
TR1
BOOLEAN
Trip signal from step 1
TR2
BOOLEAN
Trip signal from step 2
START
BOOLEAN
General start signal
ST1
BOOLEAN
Start signal from step 1
ST1L1
BOOLEAN
Start signal from step 1 phase L1
ST1L2
BOOLEAN
Start signal from step 1 phase L2
ST1L3
BOOLEAN
Start signal from step 1 phase L3
ST2
BOOLEAN
Start signal from step 2
9.1.5
Settings
Table 156:
UV2PTUV Group settings (basic)
Name
Values (Range)
Unit
Step
Default
Description
Operation
Off
On
-
-
Off
Operation Off / On
OperationStep1
Off
On
-
-
On
Enable execution of step 1
Characterist1
Definite time
Inverse curve A
Inverse curve B
-
-
Definite time
Selection of time delay curve type for step
1
OpMode1
1 out of 3
2 out of 3
3 out of 3
-
-
1 out of 3
Number of phases required to operate (1
of 3, 2 of 3, 3 of 3) from step 1
U1<
1 - 100
%UB
1
70
Voltage start value (DT & IDMT) in % of
UBase for step 1
t1
0.00 - 6000.00
s
0.01
5.00
Definite time delay of step 1
t1Min
0.000 - 60.000
s
0.001
5.000
Minimum operate time for inverse curves
for step 1
k1
0.05 - 1.10
-
0.01
0.05
Time multiplier for the inverse time delay
for step 1
Table continues on next page
Section 9
1MRK 502 048-UEN A
Voltage protection
258
Technical manual
Summary of Contents for REG650 ANSI
Page 1: ...Relion 650 series Generator protection REG650 Technical manual ...
Page 2: ......
Page 36: ...30 ...
Page 42: ...36 ...
Page 50: ...44 ...
Page 64: ...58 ...
Page 86: ...80 ...
Page 262: ...256 ...
Page 300: ...294 ...
Page 438: ...432 ...
Page 476: ...470 ...
Page 592: ...586 ...
Page 664: ...658 ...
Page 678: ...672 ...
Page 726: ...720 ...
Page 727: ...721 ...