Table 211:
SESRSYN Non group settings (basic)
Name
Values (Range)
Unit
Step
Default
Description
GblBaseSelBus
1 - 6
-
1
1
Selection of one of the Global Base Value
groups, Bus
GblBaseSelLine
1 - 6
-
1
1
Selection of one of the Global Base Value
groups, Line
SelPhaseBus1
Phase L1
Phase L2
Phase L3
Phase L1L2
Phase L2L3
Phase L3L1
Positive sequence
-
-
Phase L1
Select phase for busbar1
SelPhaseBus2
Phase L1
Phase L2
Phase L3
Phase L1L2
Phase L2L3
Phase L3L1
Positive sequence
-
-
Phase L1
Select phase for busbar2
SelPhaseLine1
Phase L1
Phase L2
Phase L3
Phase L1L2
Phase L2L3
Phase L3L1
Positive sequence
-
-
Phase L1
Select phase for line1
SelPhaseLine2
Phase L1
Phase L2
Phase L3
Phase L1L2
Phase L2L3
Phase L3L1
Positive sequence
-
-
Phase L1
Select phase for line2
12.1.6
Monitored data
Table 212:
SESRSYN Monitored data
Name
Type
Values (Range)
Unit
Description
UDIFFME
REAL
-
-
Calculated difference of
voltage in p.u of set
voltage base value
FRDIFFME
REAL
-
Hz
Calculated difference of
frequency
PHDIFFME
REAL
-
deg
Calculated difference of
phase angle
UBUS
REAL
-
kV
Bus voltage
ULINE
REAL
-
kV
Line voltage
Section 12
1MRK 502 048-UEN A
Control
326
Technical manual
Summary of Contents for REG650 ANSI
Page 1: ...Relion 650 series Generator protection REG650 Technical manual ...
Page 2: ......
Page 36: ...30 ...
Page 42: ...36 ...
Page 50: ...44 ...
Page 64: ...58 ...
Page 86: ...80 ...
Page 262: ...256 ...
Page 300: ...294 ...
Page 438: ...432 ...
Page 476: ...470 ...
Page 592: ...586 ...
Page 664: ...658 ...
Page 678: ...672 ...
Page 726: ...720 ...
Page 727: ...721 ...