Name
Type
Description
BC12OPTR
BOOLEAN
No connection via the own bus coupler between
WA1 and WA2
BC12CLTR
BOOLEAN
Connection exists via the own bus coupler between
WA1 and WA2
BC17OPTR
BOOLEAN
No connection via the own bus coupler between
WA1 and WA7
BC17CLTR
BOOLEAN
Connection exists via the own bus coupler between
WA1 and WA7
BC27OPTR
BOOLEAN
No connection via the own bus coupler between
WA2 and WA7
BC27CLTR
BOOLEAN
Connection exists via the own bus coupler between
WA2 and WA7
VPQB1TR
BOOLEAN
Switch status of QB1 is valid (open or closed)
VQB220TR
BOOLEAN
Switch status of QB2 and QB20 are valid (open or
closed)
VPQB7TR
BOOLEAN
Switch status of QB7 is valid (open or closed)
VPQB12TR
BOOLEAN
Switch status of QB1 and QB2 are valid (open or
closed)
VPBC12TR
BOOLEAN
Status of the bus coupler apparatuses between
WA1 and WA2 are valid
VPBC17TR
BOOLEAN
Status of the bus coupler apparatuses between
WA1 and WA7 are valid
VPBC27TR
BOOLEAN
Status of the bus coupler apparatuses between
WA2 and WA7 are valid
12.3.6.6
Settings
The function does not have any settings available in Local HMI or Protection and
Control IED Manager (PCM600).
12.3.7
Interlocking for 1 1/2 CB BH
12.3.7.1
Identification
Function description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Interlocking for 1 1/2 breaker diameter
BH_CONN
-
3
Interlocking for 1 1/2 breaker diameter
BH_LINE_A
-
3
Interlocking for 1 1/2 breaker diameter
BH_LINE_B
-
3
Section 12
1MRK 502 048-UEN A
Control
372
Technical manual
Summary of Contents for REG650 ANSI
Page 1: ...Relion 650 series Generator protection REG650 Technical manual ...
Page 2: ......
Page 36: ...30 ...
Page 42: ...36 ...
Page 50: ...44 ...
Page 64: ...58 ...
Page 86: ...80 ...
Page 262: ...256 ...
Page 300: ...294 ...
Page 438: ...432 ...
Page 476: ...470 ...
Page 592: ...586 ...
Page 664: ...658 ...
Page 678: ...672 ...
Page 726: ...720 ...
Page 727: ...721 ...