Table 248:
BH_CONN Output signals
Name
Type
Description
QA1CLREL
BOOLEAN
Closing of QA1 is allowed
QA1CLITL
BOOLEAN
Closing of QA1 is forbidden
QB61REL
BOOLEAN
Switching of QB61 is allowed
QB61ITL
BOOLEAN
Switching of QB61 is forbidden
QB62REL
BOOLEAN
Switching of QB62 is allowed
QB62ITL
BOOLEAN
Switching of QB62 is forbidden
QC1REL
BOOLEAN
Switching of QC1 is allowed
QC1ITL
BOOLEAN
Switching of QC1 is forbidden
QC2REL
BOOLEAN
Switching of QC2 is allowed
QC2ITL
BOOLEAN
Switching of QC2 is forbidden
Table 249:
BH_LINE_A Output signals
Name
Type
Description
QA1CLREL
BOOLEAN
Closing of QA1 is allowed
QA1CLITL
BOOLEAN
Closing of QA1 is forbidden
QB6REL
BOOLEAN
Switching of QB6 is allowed
QB6ITL
BOOLEAN
Switching of QB6 is forbidden
QB1REL
BOOLEAN
Switching of QB1 is allowed
QB1ITL
BOOLEAN
Switching of QB1 is forbidden
QC1REL
BOOLEAN
Switching of QC1 is allowed
QC1ITL
BOOLEAN
Switching of QC1 is forbidden
QC2REL
BOOLEAN
Switching of QC2 is allowed
QC2ITL
BOOLEAN
Switching of QC2 is forbidden
QC3REL
BOOLEAN
Switching of QC3 is allowed
QC3ITL
BOOLEAN
Switching of QC3 is forbidden
QB9REL
BOOLEAN
Switching of QB9 is allowed
QB9ITL
BOOLEAN
Switching of QB9 is forbidden
QC9REL
BOOLEAN
Switching of QC9 is allowed
QC9ITL
BOOLEAN
Switching of QC9 is forbidden
QB1OPTR
BOOLEAN
QB1 is in open position
QB1CLTR
BOOLEAN
QB1 is in closed position
VPQB1TR
BOOLEAN
Switch status of QB1 is valid (open or closed)
Section 12
1MRK 502 048-UEN A
Control
384
Technical manual
Summary of Contents for REG650 ANSI
Page 1: ...Relion 650 series Generator protection REG650 Technical manual ...
Page 2: ......
Page 36: ...30 ...
Page 42: ...36 ...
Page 50: ...44 ...
Page 64: ...58 ...
Page 86: ...80 ...
Page 262: ...256 ...
Page 300: ...294 ...
Page 438: ...432 ...
Page 476: ...470 ...
Page 592: ...586 ...
Page 664: ...658 ...
Page 678: ...672 ...
Page 726: ...720 ...
Page 727: ...721 ...