Table 250:
BH_LINE_B Output signals
Name
Type
Description
QA1CLREL
BOOLEAN
Closing of QA1 is allowed
QA1CLITL
BOOLEAN
Closing of QA1 is forbidden
QB6REL
BOOLEAN
Switching of QB6 is allowed
QB6ITL
BOOLEAN
Switching of QB6 is forbidden
QB2REL
BOOLEAN
Switching of QB2 is allowed
QB2ITL
BOOLEAN
Switching of QB2 is forbidden
QC1REL
BOOLEAN
Switching of QC1 is allowed
QC1ITL
BOOLEAN
Switching of QC1 is forbidden
QC2REL
BOOLEAN
Switching of QC2 is allowed
QC2ITL
BOOLEAN
Switching of QC2 is forbidden
QC3REL
BOOLEAN
Switching of QC3 is allowed
QC3ITL
BOOLEAN
Switching of QC3 is forbidden
QB9REL
BOOLEAN
Switching of QB9 is allowed
QB9ITL
BOOLEAN
Switching of QB9 is forbidden
QC9REL
BOOLEAN
Switching of QC9 is allowed
QC9ITL
BOOLEAN
Switching of QC9 is forbidden
QB2OPTR
BOOLEAN
QB2 is in open position
QB2CLTR
BOOLEAN
QB2 is in closed position
VPQB2TR
BOOLEAN
Switch status of QB2 is valid (open or closed)
12.3.7.6
Settings
The function does not have any settings available in Local HMI or Protection and
Control IED Manager (PCM600).
12.3.8
Interlocking for double CB bay DB
12.3.8.1
Identification
Function description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Interlocking for double CB bay
DB_BUS_A
-
3
Interlocking for double CB bay
DB_BUS_B
-
3
Interlocking for double CB bay
DB_LINE
-
3
1MRK 502 048-UEN A
Section 12
Control
385
Technical manual
Summary of Contents for REG650 ANSI
Page 1: ...Relion 650 series Generator protection REG650 Technical manual ...
Page 2: ......
Page 36: ...30 ...
Page 42: ...36 ...
Page 50: ...44 ...
Page 64: ...58 ...
Page 86: ...80 ...
Page 262: ...256 ...
Page 300: ...294 ...
Page 438: ...432 ...
Page 476: ...470 ...
Page 592: ...586 ...
Page 664: ...658 ...
Page 678: ...672 ...
Page 726: ...720 ...
Page 727: ...721 ...