14.9.6
Technical data
Table 403:
DRPRDRE technical data
Function
Value
Buffer capacity
Maximum number of analog inputs
40
Maximum number of binary inputs
96
Maximum number of disturbance reports
100
Maximum total recording time (3.4 s recording time and maximum number of
channels, typical value)
340 seconds (100
recordings) at 50 Hz
280 seconds (80
recordings) at 60 Hz
14.10
IEC 61850 generic communication I/O functions
SPGGIO
14.10.1
Identification
Function description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
IEC 61850 generic communication I/O
functions
SPGGIO
-
-
14.10.2
Functionality
IEC61850 generic communication I/O functions SPGGIO is used to send one single
logical signal to other systems or equipment in the substation.
14.10.3
Function block
SPGGIO
BLOCK
^IN
IEC09000237_en_1.vsd
IEC09000237 V1 EN
Figure 257:
SPGGIO function block
14.10.4
Signals
Table 404:
SPGGIO Input signals
Name
Type
Default
Description
BLOCK
BOOLEAN
0
Block of function
IN
BOOLEAN
0
Input status
Section 14
1MRK 502 048-UEN A
Monitoring
544
Technical manual
Summary of Contents for REG650 ANSI
Page 1: ...Relion 650 series Generator protection REG650 Technical manual ...
Page 2: ......
Page 36: ...30 ...
Page 42: ...36 ...
Page 50: ...44 ...
Page 64: ...58 ...
Page 86: ...80 ...
Page 262: ...256 ...
Page 300: ...294 ...
Page 438: ...432 ...
Page 476: ...470 ...
Page 592: ...586 ...
Page 664: ...658 ...
Page 678: ...672 ...
Page 726: ...720 ...
Page 727: ...721 ...