Name
Values (Range)
Unit
Step
Default
Description
MV lLim
-5000.00 - 5000.00
xBase
0.01
-800.00
Low limit multiplied with the base prefix
(multiplication factor)
MV llLim
-5000.00 - 5000.00
xBase
0.01
-900.00
Low Low limit multiplied with the base
prefix (multiplication factor)
MV min
-5000.00 - 5000.00
xBase
0.01
-1000.00
Minimum value multiplied with the base
prefix (multiplication factor)
MV max
-5000.00 - 5000.00
xBase
0.01
1000.00
Maximum value multiplied with the base
prefix (multiplication factor)
MV dbType
Cyclic
Dead band
Int deadband
-
-
Dead band
Reporting type
MV limHys
0.000 - 100.000
%
0.001
5.000
Hysteresis value in % of range (common
for all limits)
14.12.6
Monitored data
Table 410:
MVGGIO Monitored data
Name
Type
Values (Range)
Unit
Description
VALUE
REAL
-
-
Magnitude of deadband
value
RANGE
INTEGER
0=Normal
1=High
2=Low
3=High-High
4=Low-Low
-
Range
14.12.7
Operation principle
Upon receiving an analog signal at its input, IEC61850 generic communication I/O
functions (MVGGIO) will give the instantaneous value of the signal and the range, as
output values. In the same time, it will send over IEC 61850-8-1 the value, to other IEC
61850 clients in the substation.
14.13
Measured value expander block MVEXP
14.13.1
Identification
Function description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Measured value expander block
MVEXP
-
-
1MRK 502 048-UEN A
Section 14
Monitoring
549
Technical manual
Summary of Contents for REG650 ANSI
Page 1: ...Relion 650 series Generator protection REG650 Technical manual ...
Page 2: ......
Page 36: ...30 ...
Page 42: ...36 ...
Page 50: ...44 ...
Page 64: ...58 ...
Page 86: ...80 ...
Page 262: ...256 ...
Page 300: ...294 ...
Page 438: ...432 ...
Page 476: ...470 ...
Page 592: ...586 ...
Page 664: ...658 ...
Page 678: ...672 ...
Page 726: ...720 ...
Page 727: ...721 ...