GlobalBaseSel
: Selects the global base value group used by the function to define
(
IBase
), (
UBase
) and (
SBase
).
14.13.6
Operation principle
The input signal must be connected to a range output of a measuring function block
(CVMMXN, CMMXU, VMMXU, VNMMXU, CMSQI, VMSQ or MVGGIO). The
function block converts the input integer value to five binary output signals according
to
.
Table 413:
Input integer value converted to binary output signals
Measured supervised
value is:
below low-low
limit
between low‐
low and low
limit
between low
and high limit
between high-
high and high
limit
above high-
high limit
Output:
LOWLOW
High
LOW
High
NORMAL
High
HIGH
High
HIGHHIGH
High
14.14
Station battery supervision SPVNZBAT
14.14.1
Identification
Function description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Station battery supervision function
SPVNZBAT
U<>
-
14.14.2
Function block
GUID-2D3C21EA-75E9-4E44-AA0F-4DEA7599182A V1 EN
Figure 260:
Function block
14.14.3
Functionality
The station battery supervision function SPVNZBAT is used for monitoring battery
terminal voltage.
1MRK 502 048-UEN A
Section 14
Monitoring
551
Technical manual
Summary of Contents for REG650 ANSI
Page 1: ...Relion 650 series Generator protection REG650 Technical manual ...
Page 2: ......
Page 36: ...30 ...
Page 42: ...36 ...
Page 50: ...44 ...
Page 64: ...58 ...
Page 86: ...80 ...
Page 262: ...256 ...
Page 300: ...294 ...
Page 438: ...432 ...
Page 476: ...470 ...
Page 592: ...586 ...
Page 664: ...658 ...
Page 678: ...672 ...
Page 726: ...720 ...
Page 727: ...721 ...