below the levels for more than the set time delays the corresponding signals,
PRES_ALM, pressure below alarm level and PRES_LO, pressure below lockout level
alarm will be obtained.
The input signal BLK_ALM is used to block the two alarms levels. The input signal
BLOCK is used to block both the alarms and the function.
14.15.7
Technical data
Table 423:
SSIMG Technical data
Function
Range or value
Accuracy
Timers
(0.000-60.000) s
± 0.5% ± 110 ms
14.16
Insulation liquid monitoring function SSIML
14.16.1
Identification
Function description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Insulation liquid monitoring function
SSIML
-
71
14.16.2
Functionality
Insulation liquid monitoring function SSIML is used for monitoring the circuit
breaker condition. Binary information based on the oil level in the circuit breaker is
used as input signals to the function. In addition, the function generates alarms based
on received information.
14.16.3
Function block
SSIML
BLOCK
BLK_ALM
LEVEL
TEMP
LVL_ALM
LEVEL_LO
SET_L_LO
SET_T_LO
RESET_LO
LEVEL
LVL_ALM
LVL_LO
TEMP
TEMP_ALM
TEMP_LO
IEC09000128-1-en.vsd
IEC09000128 V1 EN
Figure 263:
SSIML function block
1MRK 502 048-UEN A
Section 14
Monitoring
557
Technical manual
Summary of Contents for REG650 ANSI
Page 1: ...Relion 650 series Generator protection REG650 Technical manual ...
Page 2: ......
Page 36: ...30 ...
Page 42: ...36 ...
Page 50: ...44 ...
Page 64: ...58 ...
Page 86: ...80 ...
Page 262: ...256 ...
Page 300: ...294 ...
Page 438: ...432 ...
Page 476: ...470 ...
Page 592: ...586 ...
Page 664: ...658 ...
Page 678: ...672 ...
Page 726: ...720 ...
Page 727: ...721 ...