GUID-60ADC120-4B5A-40D8-B1C5-475E4634214B V1 EN
Figure 266:
Functional module diagram for monitoring circuit breaker status
BLOCK and BLK_ALM inputs
Phase current check
This module compares the three phase currents with the setting
AccDisLevel
. If the
current in a phase exceeds the set level, information about phase is reported to the
contact position indicator module.
Contact position indicator
The circuit breaker status is open if the auxiliary input contact
POSCLOSE
is low, the
POSOPEN
input is high and the current is zero. The circuit breaker is closed when the
POSOPEN
input is low and the
POSCLOSE
input is high. The breaker is in the
intermediate position if both the auxiliary contacts have the same value, that is, both
are in the logical level "0" or "1", or if the auxiliary input contact
POSCLOSE
is low
and the
POSOPEN
input is high, but the current is not zero.
The status of the breaker is indicated with the binary outputs
CBOPEN
,
CBINVPOS
and
CBCLOSED
for open, error state and closed position respectively.
14.17.7.2
Circuit breaker operation monitoring
The purpose of the circuit breaker operation monitoring subfunction is to indicate if
the circuit breaker has not been operated for a long time.
The operation of the circuit breaker operation monitoring can be described by using a
module diagram. All the modules in the diagram are explained in the next sections.
GUID-82C88B52-1812-477F-8B1A-3011A300547A V1 EN
Figure 267:
Functional module diagram for calculating inactive days and alarm
for circuit breaker operation monitoring
1MRK 502 048-UEN A
Section 14
Monitoring
565
Technical manual
Summary of Contents for REG650 ANSI
Page 1: ...Relion 650 series Generator protection REG650 Technical manual ...
Page 2: ......
Page 36: ...30 ...
Page 42: ...36 ...
Page 50: ...44 ...
Page 64: ...58 ...
Page 86: ...80 ...
Page 262: ...256 ...
Page 300: ...294 ...
Page 438: ...432 ...
Page 476: ...470 ...
Page 592: ...586 ...
Page 664: ...658 ...
Page 678: ...672 ...
Page 726: ...720 ...
Page 727: ...721 ...