14.22.2
Function block
IEC10000291-1-en.vsd
I103FLTPROT
BLOCK
64_STL1
65_STL2
66_STL3
67_STIN
68_TRGEN
69_TRL1
70_TRL2
71_TRL3
72_TRBKUP
73_SCL
74_FW
75_REV
76_TRANS
77_RECEV
78_ZONE1
79_ZONE2
80_ZONE3
81_ZONE4
82_ZONE5
84_STGEN
85_BFP
86_MTRL1
87_MTRL2
88_MTRL3
89_MTRN
90_IOC
91_IOC
92_IEF
93_IEF
ARINPROG
FLTLOC
IEC10000291 V1 EN
Figure 280:
I103FLTPROT function block
14.22.3
Signals
Table 441:
I103FLTPROT Input signals
Name
Type
Default
Description
BLOCK
BOOLEAN
0
Block of status reporting.
64_STL1
BOOLEAN
0
Information number 64, start phase L1
65_STL2
BOOLEAN
0
Information number 65, start phase L2
66_STL3
BOOLEAN
0
Information number 66, start phase L3
67_STIN
BOOLEAN
0
Information number 67, start residual current IN
68_TRGEN
BOOLEAN
0
Information number 68, trip general
69_TRL1
BOOLEAN
0
Information number 69, trip phase L1
70_TRL2
BOOLEAN
0
Information number 70, trip phase L2
71_TRL3
BOOLEAN
0
Information number 71, trip phase L3
72_TRBKUP
BOOLEAN
0
Information number 72, back up trip I>>
73_SCL
REAL
0
Information number 73, fault location in ohm
74_FW
BOOLEAN
0
Information number 74, forward/line
75_REV
BOOLEAN
0
Information number 75, reverse/busbar
Table continues on next page
Section 14
1MRK 502 048-UEN A
Monitoring
580
Technical manual
Summary of Contents for REG650 ANSI
Page 1: ...Relion 650 series Generator protection REG650 Technical manual ...
Page 2: ......
Page 36: ...30 ...
Page 42: ...36 ...
Page 50: ...44 ...
Page 64: ...58 ...
Page 86: ...80 ...
Page 262: ...256 ...
Page 300: ...294 ...
Page 438: ...432 ...
Page 476: ...470 ...
Page 592: ...586 ...
Page 664: ...658 ...
Page 678: ...672 ...
Page 726: ...720 ...
Page 727: ...721 ...