The input of this GOOSE block must be linked in SMT by means of
a cross to receive the binary values.
The implementation for IEC61850 quality data handling is restricted
to a simple level. If quality data validity is GOOD then the OUTxVAL
output will be HIGH. If quality data validity is INVALID,
QUESTIONABLE, OVERFLOW, FAILURE or OLD DATA then
the OUTxVAL output will be LOW.
16.5
GOOSE function block to receive a double point
value GOOSEDPRCV
16.5.1
Identification
Function description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
GOOSE function block to receive a
double point value
GOOSEDPRCV
-
-
16.5.2
Functionality
GOOSEDPRCV is used to receive a double point value using IEC61850 protocol via
GOOSE.
16.5.3
Function block
IEC10000249-1-en.vsd
GOOSEDPRCV
BLOCK
^DPOUT
DATAVALID
COMMVALID
TEST
IEC10000249 V1 EN
Figure 290:
GOOSEDPRCV function block
16.5.4
Signals
Table 469:
GOOSEDPRCV Input signals
Name
Type
Default
Description
BLOCK
BOOLEAN
0
Block of function
1MRK 502 048-UEN A
Section 16
Station communication
603
Technical manual
Summary of Contents for REG650 ANSI