Name
Values (Range)
Unit
Step
Default
Description
Threshold4
6 - 900
%UB
1
65
Threshold in percentage of station battery
voltage for input 4
DebounceTime4
0.000 - 0.100
s
0.001
0.005
Debounce time for input 4
OscillationCount4
0 - 255
-
1
0
Oscillation count for input 4
OscillationTime4
0.000 - 600.000
s
0.001
0.000
Oscillation time for input 4
Threshold5
6 - 900
%UB
1
65
Threshold in percentage of station battery
voltage for input 5
DebounceTime5
0.000 - 0.100
s
0.001
0.005
Debounce time for input 5
OscillationCount5
0 - 255
-
1
0
Oscillation count for input 5
OscillationTime5
0.000 - 600.000
s
0.001
0.000
Oscillation time for input 5
Threshold6
6 - 900
%UB
1
65
Threshold in percentage of station battery
voltage for input 6
DebounceTime6
0.000 - 0.100
s
0.001
0.005
Debounce time for input 6
OscillationCount6
0 - 255
-
1
0
Oscillation count for input 6
OscillationTime6
0.000 - 600.000
s
0.001
0.000
Oscillation time for input 6
Threshold7
6 - 900
%UB
1
65
Threshold in percentage of station battery
voltage for input 7
DebounceTime7
0.000 - 0.100
s
0.001
0.005
Debounce time for input 7
OscillationCount7
0 - 255
-
1
0
Oscillation count for input 7
OscillationTime7
0.000 - 600.000
s
0.001
0.000
Oscillation time for input 7
Threshold8
6 - 900
%UB
1
65
Threshold in percentage of station battery
voltage for input 8
DebounceTime8
0.000 - 0.100
s
0.001
0.005
Debounce time for input 8
OscillationCount8
0 - 255
-
1
0
Oscillation count for input 8
OscillationTime8
0.000 - 600.000
s
0.001
0.000
Oscillation time for input 8
Threshold9
6 - 900
%UB
1
65
Threshold in percentage of station battery
voltage for input 9
DebounceTime9
0.000 - 0.100
s
0.001
0.005
Debounce time for input 9
OscillationCount9
0 - 255
-
1
0
Oscillation count for input 9
OscillationTime9
0.000 - 600.000
s
0.001
0.000
Oscillation time for input 9
Threshold10
6 - 900
%UB
1
65
Threshold in percentage of station battery
voltage for input 10
DebounceTime10
0.000 - 0.100
s
0.001
0.005
Debounce time for input 10
OscillationCount10
0 - 255
-
1
0
Oscillation count for input 10
OscillationTime10
0.000 - 600.000
s
0.001
0.000
Oscillation time for input 10
Threshold11
6 - 900
%UB
1
65
Threshold in percentage of station battery
voltage for input 11
DebounceTime11
0.000 - 0.100
s
0.001
0.005
Debounce time for input 11
OscillationCount11
0 - 255
-
1
0
Oscillation count for input 11
OscillationTime11
0.000 - 600.000
s
0.001
0.000
Oscillation time for input 11
Threshold12
6 - 900
%UB
1
65
Threshold in percentage of station battery
voltage for input 12
Table continues on next page
Section 4
1MRK 502 048-UEN A
Binary input and output modules
56
Technical manual
Summary of Contents for REG650 ANSI
Page 1: ...Relion 650 series Generator protection REG650 Technical manual ...
Page 2: ......
Page 36: ...30 ...
Page 42: ...36 ...
Page 50: ...44 ...
Page 64: ...58 ...
Page 86: ...80 ...
Page 262: ...256 ...
Page 300: ...294 ...
Page 438: ...432 ...
Page 476: ...470 ...
Page 592: ...586 ...
Page 664: ...658 ...
Page 678: ...672 ...
Page 726: ...720 ...
Page 727: ...721 ...