17.2
Time synchronization
17.2.1
Functionality
The time synchronization source selector is used to select a common source of
absolute time for the IED when it is a part of a protection system. This makes it
possible to compare event and disturbance data between all IEDs in a station
automation system.
Micro SCADA OPC server should not be used as a time
synchronization source.
17.2.2
Time synchronization TIMESYNCHGEN
17.2.2.1
Identification
Function description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Time synchronization
TIMESYNCHGE
N
-
-
17.2.2.2
Settings
Table 492:
TIMESYNCHGEN Non group settings (basic)
Name
Values (Range)
Unit
Step
Default
Description
CoarseSyncSrc
Off
SNTP
DNP
IEC60870-5-103
-
-
Off
Coarse time synchronization source
FineSyncSource
Off
SNTP
IRIG-B
-
-
Off
Fine time synchronization source
SyncMaster
Off
SNTP-Server
-
-
Off
Activate IED as synchronization master
17.2.3
Time synchronization via SNTP
17.2.3.1
Identification
Function description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Time synchronization via SNTP
SNTP
-
-
Section 17
1MRK 502 048-UEN A
Basic IED functions
622
Technical manual
Summary of Contents for REG650 ANSI
Page 1: ...Relion 650 series Generator protection REG650 Technical manual ...
Page 2: ......
Page 36: ...30 ...
Page 42: ...36 ...
Page 50: ...44 ...
Page 64: ...58 ...
Page 86: ...80 ...
Page 262: ...256 ...
Page 300: ...294 ...
Page 438: ...432 ...
Page 476: ...470 ...
Page 592: ...586 ...
Page 664: ...658 ...
Page 678: ...672 ...
Page 726: ...720 ...
Page 727: ...721 ...