17.8.2
Functionality
The rated system frequency and phasor rotation are set under
Main menu/
Configuration/ Power system/ Primary values/PRIMVAL
in the local HMI and
PCM600 parameter setting tree.
17.8.3
Settings
Table 508:
PRIMVAL Non group settings (basic)
Name
Values (Range)
Unit
Step
Default
Description
Frequency
50.0 - 60.0
Hz
10.0
50.0
Rated system frequency
PhaseRotation
Normal=L1L2L3
Inverse=L3L2L1
-
-
Normal=L1L2L3
System phase rotation
17.9
Signal matrix for analog inputs SMAI
17.9.1
Functionality
Signal matrix for analog inputs function (SMAI), also known as the preprocessor
function, processes the analog signals connected to it and gives information about all
aspects of the analog signals connected, like the RMS value, phase angle, frequency,
harmonic content, sequence components and so on. This information is then used by
the respective functions in ACT (for example protection, measurement or
monitoring).
The SMAI function is used within PCM600 in direct relation with the Signal Matrix
tool or the Application Configuration tool.
The SMAI function blocks for the 650 series of products are possible
to set for two cycle times either 5 or 20ms. The function blocks
connected to a SMAI function block shall always have the same cycle
time as the SMAI block.
17.9.2
Identification
Function description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Signal matrix for analog inputs
SMAI_20_x
-
-
Section 17
1MRK 502 048-UEN A
Basic IED functions
638
Technical manual
Summary of Contents for REG650 ANSI
Page 1: ...Relion 650 series Generator protection REG650 Technical manual ...
Page 2: ......
Page 36: ...30 ...
Page 42: ...36 ...
Page 50: ...44 ...
Page 64: ...58 ...
Page 86: ...80 ...
Page 262: ...256 ...
Page 300: ...294 ...
Page 438: ...432 ...
Page 476: ...470 ...
Page 592: ...586 ...
Page 664: ...658 ...
Page 678: ...672 ...
Page 726: ...720 ...
Page 727: ...721 ...