Table 575:
IEC Inverse time characteristics
Function
Range or value
Accuracy
Operating characteristic:
(
)
1
=
×
-
æ
ö
ç
÷
ç
÷
è
ø
P
A
t
k
I
EQUATION1251-SMALL V1 EN
I = I
measured
/I
set
k = (0.05-999) in steps of 0.01 -
IEC Normal Inverse
A=0.14, P=0.02
IEC Very inverse
A=13.5, P=1.0
IEC Inverse
A=0.14, P=0.02
IEC Extremely inverse
A=80.0, P=2.0
IEC Short time inverse
A=0.05, P=0.04
IEC Long time inverse
A=120, P=1.0
The parameter setting
Characterist1 and 4
/
Reserved
shall not be used,
since this parameter setting is for future use and not implemented yet.
Table 576:
RI and RD type inverse time characteristics
Function
Range or value
Accuracy
RI type inverse characteristic
1
0.236
0.339
=
×
-
t
k
I
EQUATION1137-SMALL V1 EN
I = I
measured
/I
set
k = (0.05-999) in steps of 0.01
RD type logarithmic inverse characteristic
5.8
1.35
=
-
×
æ
ö
ç
÷
è
ø
t
I
In
k
EQUATION1138-SMALL V1 EN
I = I
measured
/I
set
k = (0.05-999) in steps of 0.01
Section 21
1MRK 502 048-UEN A
Time inverse characteristics
690
Technical manual
Summary of Contents for REG650 ANSI
Page 1: ...Relion 650 series Generator protection REG650 Technical manual ...
Page 2: ......
Page 36: ...30 ...
Page 42: ...36 ...
Page 50: ...44 ...
Page 64: ...58 ...
Page 86: ...80 ...
Page 262: ...256 ...
Page 300: ...294 ...
Page 438: ...432 ...
Page 476: ...470 ...
Page 592: ...586 ...
Page 664: ...658 ...
Page 678: ...672 ...
Page 726: ...720 ...
Page 727: ...721 ...