Name
Values (Range)
Unit
Step
Default
Description
OperationStep2
Off
On
-
-
On
Enable execution of step 2
OpMode2
1 out of 3
2 out of 3
3 out of 3
-
-
1 out of 3
Number of phases required to operate (1
of 3, 2 of 3, 3 of 3) from step 2
U2<
1 - 100
%UB
1
50
Voltage start value (DT & IDMT) in % of
UBase for step 2
t2
0.000 - 60.000
s
0.001
5.000
Definie time delay of step 2
Table 157:
UV2PTUV Non group settings (basic)
Name
Values (Range)
Unit
Step
Default
Description
GlobalBaseSel
1 - 6
-
1
1
Selection of one of the Global Base Value
groups
ConnType
PhN DFT
PhN RMS
PhPh DFT
PhPh RMS
-
-
PhN DFT
Group selector for connection type
9.1.6
Monitored data
Table 158:
UV2PTUV Monitored data
Name
Type
Values (Range)
Unit
Description
UL1
REAL
-
kV
Voltage in phase L1
UL2
REAL
-
kV
Voltage in phase L2
UL3
REAL
-
kV
Voltage in phase L3
9.1.7
Operation principle
Two-step undervoltage protection (UV2PTUV) is used to detect low power system
voltage. UV2PTUV has two voltage measuring steps with separate time delays. If one,
two or three phase voltages decrease below the set value, a corresponding START
signal is generated. UV2PTUV can be set to START/TRIP based on
1 out of 3
,
2 out
of 3
or
3 out of 3
of the measured voltages, being below the set point. If the voltage
remains below the set value for a time period corresponding to the chosen time delay,
the corresponding trip signal is issued. The time delay characteristic is settable for step
1 and can be either definite or inverse time delayed. Step 2 is always definite time
delayed.
UV2PTUV can be set to measure phase-to-earth fundamental value, phase-to-phase
fundamental value, phase-to-earth true RMS value or phase-to-phase true RMS value.
The choice of the measuring is done by the parameter
ConnType
. The voltage related
settings are made in percent of base voltage which is set in kV phase-to-phase voltage.
This means operation for phase-to-earth voltage under:
1MRK 502 048-UEN A
Section 9
Voltage protection
259
Technical manual
Summary of Contents for REG650 ANSI
Page 1: ...Relion 650 series Generator protection REG650 Technical manual ...
Page 2: ......
Page 36: ...30 ...
Page 42: ...36 ...
Page 50: ...44 ...
Page 64: ...58 ...
Page 86: ...80 ...
Page 262: ...256 ...
Page 300: ...294 ...
Page 438: ...432 ...
Page 476: ...470 ...
Page 592: ...586 ...
Page 664: ...658 ...
Page 678: ...672 ...
Page 726: ...720 ...
Page 727: ...721 ...