IEC08000013-3-en.vsd
UN
ST1
TR1
ST2
TR2
START
TRIP
Comparator
UN > U1>
Start
&
Trip
Output
Logic
Step 2
Phase 1
Phase 1
Timer
t2
START
Start
&
Trip
Output
Logic
Step 1
Time integrator
or Timer t1
Comparator
UN > U2>
START
TRIP
TRIP
OR
OR
IEC08000013 V3 EN
Figure 137:
Schematic design of Two step residual overvoltage protection
(ROV2PTOV)
The design of Two step residual overvoltage protection
(ROV2PTOV) is schematically described in
. UN is a
signal included in the three phase group signal U3P which shall be
connected to output AI3P of the SMAI. If a connection is made to the
4 input GRPxN (x is equal to instance number 2 to 12) on the SMAI,
UN is this signal else UN is the vectorial sum of the three inputs
GRPxL1 to GRPxL3.
Section 9
1MRK 502 048-UEN A
Voltage protection
274
Technical manual
Summary of Contents for REG650 ANSI
Page 1: ...Relion 650 series Generator protection REG650 Technical manual ...
Page 2: ......
Page 36: ...30 ...
Page 42: ...36 ...
Page 50: ...44 ...
Page 64: ...58 ...
Page 86: ...80 ...
Page 262: ...256 ...
Page 300: ...294 ...
Page 438: ...432 ...
Page 476: ...470 ...
Page 592: ...586 ...
Page 664: ...658 ...
Page 678: ...672 ...
Page 726: ...720 ...
Page 727: ...721 ...