Name
Type
Description
I2
REAL
I2 Amplitude
I2RANG
INTEGER
I2 Amplitude range
I2ANGL
REAL
I2Angle
14.1.5.4
Settings
Table 362:
CMSQI Non group settings (basic)
Name
Values (Range)
Unit
Step
Default
Description
Operation
Off
On
-
-
Off
Operation Off / On
3I0DbRepInt
1 - 300
Type
1
10
Cycl: Report interval (s), Db: In % of
range, Int Db: In %s
3I0Min
0 - 500000
A
1
0
Minimum value
3I0Max
0 - 500000
A
1
3300
Maximum value
3I0RepTyp
Cyclic
Dead band
Int deadband
-
-
Dead band
Reporting type
3I0LimHys
0.000 - 100.000
%
0.001
5.000
Hysteresis value in % of range and is
common for all limits
3I0AngDbRepInt
1 - 300
Type
1
10
Cycl: Report interval (s), Db: In % of
range, Int Db: In %s
I1DbRepInt
1 - 300
Type
1
10
Cycl: Report interval (s), Db: In % of
range, Int Db: In %s
I1Min
0 - 500000
A
1
0
Minimum value
I1Max
0 - 500000
A
1
1300
Maximum value
I1RepTyp
Cyclic
Dead band
Int deadband
-
-
Dead band
Reporting type
I1AngDbRepInt
1 - 300
Type
1
10
Cycl: Report interval (s), Db: In % of
range, Int Db: In %s
I2DbRepInt
1 - 300
Type
1
10
Cycl: Report interval (s), Db: In % of
range, Int Db: In %s
I2Min
0 - 500000
A
1
0
Minimum value
I2Max
0 - 500000
A
1
1300
Maximum value
I2RepTyp
Cyclic
Dead band
Int deadband
-
-
Dead band
Reporting type
I2LimHys
0.000 - 100.000
%
0.001
5.000
Hysteresis value in % of range and is
common for all limits
I2AngDbRepInt
1 - 300
Type
1
10
Cycl: Report interval (s), Db: In % of
range, Int Db: In %s
1MRK 502 048-UEN A
Section 14
Monitoring
483
Technical manual
Summary of Contents for REG650 ANSI
Page 1: ...Relion 650 series Generator protection REG650 Technical manual ...
Page 2: ......
Page 36: ...30 ...
Page 42: ...36 ...
Page 50: ...44 ...
Page 64: ...58 ...
Page 86: ...80 ...
Page 262: ...256 ...
Page 300: ...294 ...
Page 438: ...432 ...
Page 476: ...470 ...
Page 592: ...586 ...
Page 664: ...658 ...
Page 678: ...672 ...
Page 726: ...720 ...
Page 727: ...721 ...