Name
Values (Range)
Unit
Step
Default
Description
U1HiHiLim
0 - 2000000
V
1
96000
High High limit (physical value)
U1HiLim
0 - 2000000
V
1
86000
High limit (physical value)
U1LowLim
0 - 2000000
V
1
71000
Low limit (physical value)
U1LowLowLim
0 - 2000000
V
1
66000
Low Low limit (physical value)
U1LimHys
0.000 - 100.000
%
0.001
5.000
Hysteresis value in % of range and is
common for all limits
U2ZeroDb
0 - 100000
m%
1
500
Zero point clamping
U2HiHiLim
0 - 2000000
V
1
96000
High High limit (physical value)
U2HiLim
0 - 2000000
V
1
86000
High limit (physical value)
U2LowLim
0 - 2000000
V
1
71000
Low limit (physical value)
U2LowLowLim
0 - 2000000
V
1
66000
Low Low limit (physical value)
14.1.6.5
Monitored data
Table 369:
VMSQI Monitored data
Name
Type
Values (Range)
Unit
Description
3U0
REAL
-
kV
3U0 Amplitude
3U0ANGL
REAL
-
deg
3U0 Angle
U1
REAL
-
kV
U1 Amplitude
U1ANGL
REAL
-
deg
U1 Angle
U2
REAL
-
kV
U2 Amplitude
U2ANGL
REAL
-
deg
U2 Angle
14.1.7
Phase-neutral voltage measurement VNMMXU
14.1.7.1
Identification
Function description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Phase-neutral voltage measurement
VNMMXU
U
SYMBOL-UU V1 EN
-
14.1.7.2
Function block
The available function blocks of an IED are depending on the actual hardware (TRM)
and the logic configuration made in PCM600.
1MRK 502 048-UEN A
Section 14
Monitoring
487
Technical manual
Summary of Contents for REG650 ANSI
Page 1: ...Relion 650 series Generator protection REG650 Technical manual ...
Page 2: ......
Page 36: ...30 ...
Page 42: ...36 ...
Page 50: ...44 ...
Page 64: ...58 ...
Page 86: ...80 ...
Page 262: ...256 ...
Page 300: ...294 ...
Page 438: ...432 ...
Page 476: ...470 ...
Page 592: ...586 ...
Page 664: ...658 ...
Page 678: ...672 ...
Page 726: ...720 ...
Page 727: ...721 ...