IEC08000226-2-en.vsd
VNMMXU
U3P*
UL1
UL1RANG
UL1ANGL
UL2
UL2RANG
UL2ANGL
UL3
UL3RANG
UL3ANGL
IEC08000226 V2 EN
Figure 240:
VNMMXU function block
14.1.7.3
Signals
Table 370:
VNMMXU Input signals
Name
Type
Default
Description
U3P
GROUP
SIGNAL
-
Three phase group signal for voltage inputs
Table 371:
VNMMXU Output signals
Name
Type
Description
UL1
REAL
UL1 Amplitude, magnitude of reported value
UL1RANG
INTEGER
UL1 Amplitude range
UL1ANGL
REAL
UL1 Angle, magnitude of reported value
UL2
REAL
UL2 Amplitude, magnitude of reported value
UL2RANG
INTEGER
UL2 Amplitude range
UL2ANGL
REAL
UL2 Angle, magnitude of reported value
UL3
REAL
UL3 Amplitude, magnitude of reported value
UL3RANG
INTEGER
UL3 Amplitude range
UL3ANGL
REAL
UL3 Angle, magnitude of reported value
14.1.7.4
Settings
Table 372:
VNMMXU Non group settings (basic)
Name
Values (Range)
Unit
Step
Default
Description
Operation
Off
On
-
-
Off
Operation Mode On / Off
GlobalBaseSel
1 - 6
-
1
1
Selection of one of the Global Base Value
groups
UDbRepInt
1 - 300
Type
1
10
Cycl: Report interval (s), Db: In % of
range, Int Db: In %s
UMax
0 - 2000000
V
1
106000
Maximum value
Table continues on next page
Section 14
1MRK 502 048-UEN A
Monitoring
488
Technical manual
Summary of Contents for REG650 ANSI
Page 1: ...Relion 650 series Generator protection REG650 Technical manual ...
Page 2: ......
Page 36: ...30 ...
Page 42: ...36 ...
Page 50: ...44 ...
Page 64: ...58 ...
Page 86: ...80 ...
Page 262: ...256 ...
Page 300: ...294 ...
Page 438: ...432 ...
Page 476: ...470 ...
Page 592: ...586 ...
Page 664: ...658 ...
Page 678: ...672 ...
Page 726: ...720 ...
Page 727: ...721 ...