Section 15
Metering
15.1
Pulse counter PCGGIO
15.1.1
Identification
Function description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Pulse counter
PCGGIO
S00947 V1 EN
-
15.1.2
Functionality
Pulse counter (PCGGIO) function counts externally generated binary pulses, for
instance pulses coming from an external energy meter, for calculation of energy
consumption values. The pulses are captured by the BIO (binary input/output) module
and then read by the PCGGIO function. A scaled service value is available over the
station bus.
15.1.3
Function block
IEC09000335-2-en.vsd
PCGGIO
BLOCK
READ_VAL
BI_PULSE*
RS_CNT
INVALID
RESTART
BLOCKED
NEW_VAL
SCAL_VAL
IEC09000335 V2 EN
Figure 285:
PCGGIO function block
15.1.4
Signals
Table 449:
PCGGIO Input signals
Name
Type
Default
Description
BLOCK
BOOLEAN
0
Block of function
READ_VAL
BOOLEAN
0
Initiates an additional pulse counter reading
BI_PULSE
BOOLEAN
0
Connect binary input channel for metering
RS_CNT
BOOLEAN
0
Resets pulse counter value
1MRK 502 048-UEN A
Section 15
Metering
587
Technical manual
Summary of Contents for REG650 ANSI
Page 1: ...Relion 650 series Generator protection REG650 Technical manual ...
Page 2: ......
Page 36: ...30 ...
Page 42: ...36 ...
Page 50: ...44 ...
Page 64: ...58 ...
Page 86: ...80 ...
Page 262: ...256 ...
Page 300: ...294 ...
Page 438: ...432 ...
Page 476: ...470 ...
Page 592: ...586 ...
Page 664: ...658 ...
Page 678: ...672 ...
Page 726: ...720 ...
Page 727: ...721 ...