19.5
Signal outputs
Table 556:
Signal output and IRF output
Description
Value
Rated voltage
250 V AC/DC
Continuous contact carry
5 A
Make and carry for 3.0 s
10 A
Make and carry 0.5 s
30 A
Breaking capacity when the control-circuit time
constant L/R<40 ms, at U< 48/110/220 V DC
≤0.5 A/≤0.1 A/≤0.04 A
19.6
Power outputs
Table 557:
Power output relays without TCS function
Description
Value
Rated voltage
250 V AC/DC
Continuous contact carry
8 A
Make and carry for 3.0 s
15 A
Make and carry for 0.5 s
30 A
Breaking capacity when the control-circuit time
constant L/R<40 ms, at U< 48/110/220 V DC
≤1 A/≤0.3 A/≤0.1 A
Table 558:
Power output relays with TCS function
Description
Value
Rated voltage
250 V DC
Continuous contact carry
8 A
Make and carry for 3.0 s
15 A
Make and carry for 0.5 s
30 A
Breaking capacity when the control-circuit time
constant L/R<40 ms, at U< 48/110/220 V DC
≤1 A/≤0.3 A/≤0.1 A
Control voltage range
20...250 V DC
Current drain through the supervision circuit
~1.0 mA
Minimum voltage over the TCS contact
20 V DC
1MRK 502 048-UEN A
Section 19
Technical data
675
Technical manual
Summary of Contents for REG650 ANSI
Page 1: ...Relion 650 series Generator protection REG650 Technical manual ...
Page 2: ......
Page 36: ...30 ...
Page 42: ...36 ...
Page 50: ...44 ...
Page 64: ...58 ...
Page 86: ...80 ...
Page 262: ...256 ...
Page 300: ...294 ...
Page 438: ...432 ...
Page 476: ...470 ...
Page 592: ...586 ...
Page 664: ...658 ...
Page 678: ...672 ...
Page 726: ...720 ...
Page 727: ...721 ...