X1
X
R (Ohm/phase)
50%
80%
1
2
3
4
5
6
7
8
9
10
11
80% of RLdFw
40% of RLdFw
0.5 x RFPP
12
13
120°
20°
a
c
IEC05000368-3-en
b =
Ar
gLD
IEC05000368 V3 EN
Figure 31:
Distance protection characteristic with test points for phase-to-phase
measurements
Table 12:
Test points for phase-to-phase loops L1-L2 (Ohm/Loop)
Test point
Reach
Set value
Comments
1
X
X1
set
R
0
2
X
X1
set
R
R1
set
3
X
0.8 x X1
set
R
0.8 x R1
set
+ RFPP/2
4
X
0.5 x X1
set
R
0.5 x R1
set
+ RFPP/2
5
X
0.85 x RFPP x tan (ArgLd)
ArgLd = angle for the maximal load
transfer
R
0.85 x RFPP
6
X
RLdFw x tan (ArgLd)
R
RLdFw
7
X
0
R
RLdFw
8
X
–0.2143 x RFPP/2
Exact: 0.8 x RFPP/2 (ArgDir=20°)
R
0.8 x RFPP/2
9
X
–0.4 x RLdFw x tan(ArgDir=20°)
R
0.4 x RLdFw
10
X
0.5 x X1
set
Exact –0.5 x R1
set
x
tan(ArgNegRes=30°)
R
–0.23 x X1
set
Table continues on next page
1MRK502053-UEN B
Section 12
Testing functionality by secondary injection
Generator protection REG670 2.0 IEC
111
Commissioning manual
Summary of Contents for REG670 2.0 IEC
Page 1: ...Relion 670 series Generator protection REG670 2 0 IEC Commissioning manual ...
Page 2: ......
Page 16: ...10 ...
Page 30: ...24 ...
Page 58: ...52 ...
Page 62: ...56 ...
Page 76: ...70 ...
Page 90: ...84 ...
Page 94: ...88 ...
Page 108: ...102 ...
Page 246: ...240 ...
Page 252: ...246 ...
Page 267: ...261 ...