The internal events in this list not only refer to faults in the IED, but also to other
activities, such as change of settings, clearing of disturbance reports, and loss of
external time synchronization.
The information can only be retrieved from the Parameter Setting software package.
The PC can be connected either to the port at the front or at the rear of the IED.
These events are logged as internal events.
Table 20:
Events available for the internal event list in the IED
Event message:
Description
Generating signal:
INT--FAIL
Off
Internal fail status
INT--FAIL (reset event)
INT--FAIL
INT--FAIL (set event)
INT--WARNING
Off
Internal warning status
lNT--WARNING (reset event)
INT--WARNING
lNT--WARNING (set event)
IOn--Error
Off
In/Out module No. n status
IOn--Error (reset event)
IOn--Error
IOn--Error (set event)
ADMn-Error
Off
Analog/Digital module No. n
status
ADMn-Error (reset event)
ADMn-Error
ADMn-Error (set event)
MIM1-Error
Off
mA-input module status
MIM1-Error (reset event)
MIM1-Error
MIM1-Error (set event)
INT--RTC
Off
Real Time Clock (RTC) status
INT--RTC (reset event)
INT--RTC
INT--RTC (set event)
INT--TSYNC
Off
External time synchronization
status
INT--TSYNC (reset event)
INT--TSYNC
INT--TSYNC (set event)
INT--SETCHGD
Any settings in IED changed
DRPC-CLEARED
All disturbances in Disturbance
report cleared
The events in the internal event list are time tagged with a resolution of 1ms.
This means that, when using the PC for fault tracing, it provides information on the:
•
Module that should be changed.
•
Sequence of faults, if more than one unit is faulty.
•
Exact time when the fault occurred.
15.3
Repair instruction
Never disconnect the secondary connection of a current transformer
circuit without short-circuiting the transformer’s secondary winding.
Operating a current transformer with the secondary winding open will
Section 15
1MRK502053-UEN B
Troubleshooting
250
Generator protection REG670 2.0 IEC
Commissioning manual
Summary of Contents for REG670 2.0 IEC
Page 1: ...Relion 670 series Generator protection REG670 2 0 IEC Commissioning manual ...
Page 2: ......
Page 16: ...10 ...
Page 30: ...24 ...
Page 58: ...52 ...
Page 62: ...56 ...
Page 76: ...70 ...
Page 90: ...84 ...
Page 94: ...88 ...
Page 108: ...102 ...
Page 246: ...240 ...
Page 252: ...246 ...
Page 267: ...261 ...