2.
Cancel a zoom in the following ways:
•
Right click a graph and select
Cancel Zoom
in the shortcut menu.
The graph area is squeezed to the original size.
•
Press
Esc
.
3.
Enable X and Y zooming
•
To enable and disable X zooming, right click the graph and select or
deselect
Enable X zooming
in the shortcut menu.
•
To enable and disable Y zooming, right click the graph and select or
deselect
Enable Y zooming
in the shortcut menu.
7.9
Logging measurements to file
In addition to viewing online plotted data under the Monitoring tab, it is also possible
to log quantities to a file (tabbed text file) that can be viewed in the graph. Besides this
voltage levels measured by the function and also error codes are logged. This file can
then be imported to other tools for deeper analysis when needed. The logger feature is
available on the lower right corner of the Monitoring tab. Note that the logger is
independent of graph plotting.
1.
Select the
Browse
button.
See figure
2.
Navigate to a desired folder.
3.
Type a suitable file name for the .txt file and select
Save
.
4.
To start logging to this file, select the
Start
button.
ICT continuously logs data to this file with logging interval set under graph
update period. Notice that there is a field named Log period and its default value
is 1 hour. The period can be adjusted before the logging is started, if needed.
5.
The logging can be stopped by selecting the
Stop
button.
6.
You can open the file in notepad or MS Excel.
1MRK502053-UEN B
Section 7
Calibrating injection based 100% stator earth fault protection
Generator protection REG670 2.0 IEC
83
Commissioning manual
Summary of Contents for REG670 2.0 IEC
Page 1: ...Relion 670 series Generator protection REG670 2 0 IEC Commissioning manual ...
Page 2: ......
Page 16: ...10 ...
Page 30: ...24 ...
Page 58: ...52 ...
Page 62: ...56 ...
Page 76: ...70 ...
Page 90: ...84 ...
Page 94: ...88 ...
Page 108: ...102 ...
Page 246: ...240 ...
Page 252: ...246 ...
Page 267: ...261 ...