be considered as WA2 and LINE2 as LINE1. The voltage is selected by activation of
different inputs in the voltage selection logic as shown in table
and figure
.
Table 17:
Voltage selection logic
SESRSYN
CBConfig
setting
Section to
be
synchroniz
ed
Activated
B1QCLD
input on
IED from
Activated
B2QCLD
input on
IED from
Activated
LN1QCLD
input on
IED from
Activated
LN2QCLD
input on
IED from
Indication
from
SESRSYN
on IED
SESRSYN 1
(Operates on
WA1_QA1)
1 ½ bus
CB
WA1 –
LINE1
LINE1_Q
B9
B1SEL,
LN1SEL
WA1 –
LINE2
TIE_QA1
LINE2_Q
B9
B1SEL,
LN2SEL
WA1 –
WA2
TIE_QA1
WA2_QA
1
B1SEL,
B2SEL
SESRSYN 2
(Operates on
TIE_QA1)
Tie CB
LINE1 –
LINE2
LINE1_Q
B9
LINE2_Q
B9
LN1SEL,
LN2SEL
WA1 –
LINE2
WA1_QA
1
LINE2_Q
B9
B1SEL,
LN2SEL
WA2 –
LINE1
WA2_QA
1
LINE1_Q
B9
B2SEL,
LN1SEL
WA1 –
WA2
WA1_QA
1
WA2_QA
1
B1SEL,
B2SEL
SESRSYN 3
(Operates on
WA2_QA1)
1 ½ bus
alt. CB
(mirrored)
WA2 –
LINE2
LINE2_Q
B9
B2SEL,
LN2SEL
WA2 –
LINE1
TIE_QA1
LINE1_Q
B9
B2SEL,
LN1SEL
WA2 –
WA1
TIE_QA1
WA1_QA
1
B1SEL,
B2SEL
Section 12
1MRK502053-UEN B
Testing functionality by secondary injection
210
Generator protection REG670 2.0 IEC
Commissioning manual
Summary of Contents for REG670 2.0 IEC
Page 1: ...Relion 670 series Generator protection REG670 2 0 IEC Commissioning manual ...
Page 2: ......
Page 16: ...10 ...
Page 30: ...24 ...
Page 58: ...52 ...
Page 62: ...56 ...
Page 76: ...70 ...
Page 90: ...84 ...
Page 94: ...88 ...
Page 108: ...102 ...
Page 246: ...240 ...
Page 252: ...246 ...
Page 267: ...261 ...