5.2
Configuring analog CT inputs
The analog input channels must be configured to get correct measurement results as
well as correct protection functionality. Because all protection algorithms in the IED
utilize the primary system quantities, it is extremely important to make sure that
connected current transformer settings are done properly. These data are calculated by
the system engineer and normally set by the commissioner from the local HMI or from
PCM600.
The analog inputs on the transformer input module are dimensioned for either 1A or
5A. Each transformer input module has a unique combination of current and voltage
inputs. Make sure the input current rating is correct and that it matches the order
documentation.
The primary CT data are entered via the HMI menu under
Main menu/Settings/
General Settings/Analog modules/AnalogInputs
The following parameter shall be set for every current transformer connected to the
IED:
Table 3:
CT configuration
Parameter description
Parameter name
Range
Default
Rated CT primary current in A
CT Prim Input
from 0 to 99999
3000
This parameter defines the primary rated current of the CT. For two set of CTs with
ratio 1000/1 and 1000/5 this parameter is set to the same value of 1000 for both CT
inputs. The parameter
CTStarPoint
can be used in order to reverse the direction of the
CT. This might be necessary if two sets of CTs have different star point locations in
relation to the protected busbar.
For main CTs with 2A rated secondary current, it is recommended to connect the
secondary wiring to the 1A input.
Take the rated permissive overload values for the current inputs into
consideration.
5.3
Supervision of input/output modules
I/O modules configured with PCM600 (BIM, BOM or IOM) are supervised.
I/O modules that are not configured are not supervised.
Section 5
1MRK502053-UEN B
Configuring the IED and changing settings
54
Generator protection REG670 2.0 IEC
Commissioning manual
Summary of Contents for REG670 2.0 IEC
Page 1: ...Relion 670 series Generator protection REG670 2 0 IEC Commissioning manual ...
Page 2: ......
Page 16: ...10 ...
Page 30: ...24 ...
Page 58: ...52 ...
Page 62: ...56 ...
Page 76: ...70 ...
Page 90: ...84 ...
Page 94: ...88 ...
Page 108: ...102 ...
Page 246: ...240 ...
Page 252: ...246 ...
Page 267: ...261 ...