REJ 523
Technical Reference Manual
ABB Substation Automation
Products and Systems
MRS750940-MUM
38
Table 4.1.9.2-3 Event codes E9…E16
Code
Event
Weighting factor
Default value
E9
PO1 activated
1
1
E10
PO1 reset
2
1
E11
PO2 activated
4
0
E12
PO2 reset
8
0
E13
SO1 activated
16
0
E14
SO1 reset
32
0
E15
SO2 activated
64
0
E16
SO2 reset
128
0
Default value of event mask V156
3
Table 4.9.1.2-4 Event code E31
Code
Event
Weighting factor
Default value
E31
Disturbance recorder
triggered and finished
recording
1
1
Default value of event mask V157
1
Table 4.1.9.2-5 Event codes E50 and E51
Code
Event
E50
Restart of relay
E51
Overflow of event register
Explanations for default values:
0
not included in event reporting
1
included in event reporting
Summary of Contents for REJ 523