I.L. 40-386.3
(10/94)
2-19
c. Carrier Receiving Logic
(Figure 2-24)
Carrier signal from the receiver output will be directly applied to AND-47 to disable the
pilot tripping function.
d. Channel Indication
(not shown in Figure 2-24)
Since the carrier channel turns “ON” for external faults only, the channel indicators
(Car Send and Rx Ch1) should not be sealed-in.
†
e. Channel Simulation
Same as for POTT scheme.
f.
Programmable Reclosing Initiation
(Figure 2-19)
Same as for POTT scheme.
2.5.2
Pilot Ground Overcurrent
Pilot Ground Overcurrent is more dependable on high resistance faults because it is
supplemented with FDOG and IOM
(refer to
Figure 2-25
).
Pilot ground is more secure on POTT/unblocking schemes on some special power sys-
tem conditions, such as shown in
Figure 2-26
. A ØØG fault is on the paralleled line
section. Due to the system condition, fault current flows in the protected line would
be I1+I2 from A to B, and Io from B to A. The operation of pilot distance relays would
be a phase relay at A and a ground relay at B. The result would be erroneous direc-
tional comparison of an external fault as an “internal” one. The POTT/unblocking
scheme will incorrectly trip out of the protected line.
REL 302 POTT/Unblocking pilot ground unit
(PLTG/FDOG)
is supervised by the re-
verse-looking ground unit
(RDOG)
. The “Reverse-Block” logic is
as shown in Figure 2-
31.
At terminal A, the RDOG disables the PLTG/FDOG trip/key functions via AND-35
and AND-30. At terminal B, it will receive no carrier signal for permissive trip. The re-
verse-block logic also provides the conventional TBM feature to prevent false operation
on power reversal. It should be noted that a “Block-the-Block” logic is also included in
the circuit,
as shown in Figure 2-31
. The Block-the-Block logic is to prevent the Re-
verse-Block logic from over-blocking
(see the following system condition)
. If the breaker
is unequal-pole closing on a ØG fault, say pole-A, pole B and C close at a later time
(refer to Figure 2-27).
If, due to breaker contact asymmetry, the first breaker contact to
close is the one of the faulted-phase, the zero-sequence (or Negative Sequ) polarizing
voltage will initially have a polarity opposite to its fault-derived polarity, the reverse-
looking ground unit could pick-up for a short period, issue a blocking order, and main-
tain it for 50 ms consequently, the correct tripping will be delayed. The Block-the-
Block logic would prevent this delaying. The Reverse-Block logic also includes the re-
verse looking Zone3Ø /Z3G units
as shown in Figure 2-31
.
2.5.3
High Resistance Ground Fault Supplement
Supplemental protection is provided on overreaching pilot systems to detect high re-
sistance ground faults. The instantaneous forward directional overcurrent ground
†
Refer to Table 4-1 for Setting Cross-reference.
Summary of Contents for REL 301
Page 1: ......
Page 8: ......
Page 17: ...I L 40 386 3 1 10 10 94 2682F39 Sheet 1 of 2 Sub 2 Figure 1 2 REL 301 302 Layout Vertical...
Page 18: ...I L 40 386 3 10 94 1 11 2682F39 Sheet 2 of 2 Sub 2 Figure 1 3 REL 301 302 Layout Horizontal...
Page 19: ......
Page 20: ......
Page 44: ......
Page 46: ......
Page 48: ......
Page 49: ......
Page 51: ......
Page 53: ......
Page 54: ......
Page 55: ......
Page 56: ......
Page 57: ......
Page 60: ......
Page 62: ...I L 40 386 3 10 94 2 41 Figure 2 32 CO 2 Curve Characteristics 619596 Sub 2...
Page 63: ...I L 40 386 3 2 42 10 94 Figure 2 33 CO 5 Curve Characteristic 619597 Sub 2...
Page 64: ...I L 40 386 3 10 94 2 43 Figure 2 34 CO 6 Curve Characteristic 619598 Sub 2...
Page 65: ...I L 40 386 3 2 44 10 94 Figure 2 35 CO 7 Curve Characteristic 619599 Sub 2...
Page 66: ...I L 40 386 3 10 94 2 45 Figure 2 36 CO 8 Curve Characteristic 619600 Sub 2...
Page 67: ...I L 40 386 3 2 46 10 94 Figure 2 37 CO 9 Curve Characteristic 619601 Sub 2...
Page 68: ...I L 40 386 3 10 94 2 47 Figure 2 38 CO 11 Curve Characteristic 619602 Sub 2...