I.L. 40-386.3
3-10
(10/94)
The fault distance calculation is as follows:
Where Z
S
is the secondary impedance magnitude, and FANG is the fault angle.
3.3.9
Distance Type (DistUnit) Setting
Distance type has a selection of MILE and KM. It should be selected to match with the
setting of
X / Dist
. For this example, select
DistUnit
= MILE.
3.3.10 Reclosing Mode (RI Type) Setting
RI Type
is for selecting the reclosing mode. It has four selecting positions (No RI/ ØG
RI / ØØ, ØG RI/ 3Ø, ØØ, ØG RI). Refer to the guidelines for reclosing mode program-
ming for the
RI Type
setting selection.
3.3.11 Reclose Initiation Settings
Fast RI, Zone2 RI and Zone3 RI provide the selectivity for High speed tripping unit,
Zone2 and Zone3 reclosing initiation, respectively.
3.3.12 Remote Breaker Failure, Reclose Block (RemBF RB)
For a pilot system (REL 302 only), set
RemBF RB
to YES if reclose block output for
the breaker failure squelch feature is required.
3.3.13 Remote Pilot Control (Pilot) Setting
Pilot
set to
Yes
combines with the signal of Pilot Enable (external 85CO input) and
controls the operation of pilot logic tripping and reclosing initiation. The absence of ei-
ther signal will disable the pilot system logic.
The
Pilot
setting can be set either locally from the front panel, or via the communica-
tion interface or remotely.
3.3.14 System Type Selection (SystType)
SystType
selects the desired relaying system for the application. REL 301 has two set-
ting choices:
Non Pilot
and
Zone1 Extension
. REL 302 has five setting choices:
Non Pi-
lot
,
Zone1 Extension, POTT
(permissive overreach transfer trip),
PUTT
(permissive
underreach transfer trip) and
Blocking
(directional comparison blocking). It should be
set to the desired mode of operation.
3.3.15 For The Pilot REL 302 Only
a.
3-Term. (3 terminals) setting should be selected to YES for all three terminals that apply.
b.
Weakfeed
(weakfeed terminal logic enable) selection should be set to YES for the
weakfeed terminal, if applicable.
c.
For Application Of POTT or Blocking, systems, the transient block logic is always automat-
ically enabled and is initiated by the reverse looking units. The Zone3 to Reverse Dir. and
Zone3 Ø, and Zone3 G should be set to 100% of the reverse line impedance.
Flt Dist
VT Ratio
CT Ratio
--------------------------
Z
S
FANG
∠
sin
×
X
/
Dist
--------------------------------------------
×
=
Summary of Contents for REL 301
Page 1: ......
Page 8: ......
Page 17: ...I L 40 386 3 1 10 10 94 2682F39 Sheet 1 of 2 Sub 2 Figure 1 2 REL 301 302 Layout Vertical...
Page 18: ...I L 40 386 3 10 94 1 11 2682F39 Sheet 2 of 2 Sub 2 Figure 1 3 REL 301 302 Layout Horizontal...
Page 19: ......
Page 20: ......
Page 44: ......
Page 46: ......
Page 48: ......
Page 49: ......
Page 51: ......
Page 53: ......
Page 54: ......
Page 55: ......
Page 56: ......
Page 57: ......
Page 60: ......
Page 62: ...I L 40 386 3 10 94 2 41 Figure 2 32 CO 2 Curve Characteristics 619596 Sub 2...
Page 63: ...I L 40 386 3 2 42 10 94 Figure 2 33 CO 5 Curve Characteristic 619597 Sub 2...
Page 64: ...I L 40 386 3 10 94 2 43 Figure 2 34 CO 6 Curve Characteristic 619598 Sub 2...
Page 65: ...I L 40 386 3 2 44 10 94 Figure 2 35 CO 7 Curve Characteristic 619599 Sub 2...
Page 66: ...I L 40 386 3 10 94 2 45 Figure 2 36 CO 8 Curve Characteristic 619600 Sub 2...
Page 67: ...I L 40 386 3 2 46 10 94 Figure 2 37 CO 9 Curve Characteristic 619601 Sub 2...
Page 68: ...I L 40 386 3 10 94 2 47 Figure 2 38 CO 11 Curve Characteristic 619602 Sub 2...