7.
Functional Tests - Phase Comparison and Communication Interface Test
Step 1.
Enter the following settings:
Step 2.
Power the Unit Down
Step 3.
Make the following connections on the rear of REL 352:
Step 4.
Remove inner chassis
a)
Note Factory Settings of jumpers on Interconnect and Contact Input modules
b)
Make sure that the jumpers; JMP4, JMP5 and JMP6 on Contact Input module and JMP7
on Interconnect module are set for the desired battery voltage.
Freq
=
60
RP
=
NO
CTYP
=
5
CTR
=
5000
VTR
=
7000
OSC
=
TRIP
FDAT
=
TRIP
TRGG
=
3.00
TRGP
=
3.00
CD
=
dI
RBEN
= ALRB
UNBK
=
OUT
CNT
= 1CNT
ARMT
=
0
LP
=
0.50
FD2
=
1.00
IPL
=
0.50
IPH
=
OUT
IGL
=
0.50
IGH
=
OUT
IKEY
=
0.50
TERM
= 2TRM
COMM =
3ST
CINT
=
----
C0
=
1.0
C1
=
1.0
C2
=
1.0
LDT1
=
0.000
LDT2
=
0.000
XPUD
=
1.500
DTYP
=
KM
PANG
=
75
GANG
=
75
ZR
=
31.00
BKUP
=
OUT
LOPB
=
NO
FDOP
=
IN
FDOG
=
IN
DIRU
= ZSEQ
IOM
=
0.5
TOG
=
BLK
Z2P
=
4.0
T2P
=
0.1
Z2GF
=
4.0
Z2GR
=
2.0
T2G
=
0.1
Z3P
=
7.0
T3P
=
1.0
Z3GF
=
7.0
Z3GR
=
3.5
T3G
=
1.0
OST
= WAYO
OSB
= BOTH
RT
=
2.0
RU
=
4.0
OST1
=
2
OST2
=
3
OST3
=
3
OSOT
=
100
11
12
13
7
8
9
10
XMTR BAT (+)
XMTR KEY (+)
XMTR RETURN (-)
SPACE 1 (+)
MARK 1 (+)
CHAN FAIL 1 (+)
RCVR 1 RETURN (-)
(-)
(+)
TO BATTERY
DO NOT CONNECT UNTIL
CHECKS IN STEP 4.2 ARE
PERFORMED
TB4
TB5