I.L. 40-201.9
Power Automation and Protection Division
I-8
REL 352 Version 1.00
Zone 2 Phase (Z2P) unit should operate for all of the above tests. The trip times should be greater than 100
milliseconds.
For Zone 3 trips outside Zone 2 reach, the following quantities should be applied:
The REL 352 should trip and the tripping time should be 1.0
±
5% seconds. Zone 3 phase (Z3P) unit should op-
erate for all of the above tests.
For forward external faults apply the following quantities:
The REL 352 should not trip.
The following quantities simulate reverse phase-to-phase faults:
V
I
Z app
AB
Va = 35
∠
0
Vb = 35
∠
-120
Vc = 69
∠
+120
Ia = 5
∠
-45
Ib = 5
∠
+135
Ic = 0
6.12
∠
75
BC
Va = 69
∠
0
Vb = 35
∠
-120
Vc = 35
∠
+120
Ia = 0
Ib = 5
∠
-165
Ic = 5
∠
+15
6.12
∠
75
CA
Va = 35
∠
0
Vb = 69
∠
-120
Vc = 35
∠
+120
Ia = 5
∠
-105
Ib = 0
Ic = 5
∠
+75
6.16
∠
75
V
I
AB
Va = 35
∠
0
Vb = 35
∠
-120
Vc = 69
∠
+120
Ia = 4
∠
-45
Ib = 4
∠
+135
Ic = 0
BC
Va = 69
∠
0
Vb = 35
∠
-120
Vc = 35
∠
+120
Ia = 0
Ib = 4
∠
-165
Ic = 4
∠
+15
CA
Va = 35
∠
0
Vb = 69
∠
-120
Vc = 35
∠
+120
Ia = 4
∠
-105
Ib = 0
Ic = 4
∠
+75
V
I
AB
Va = 35
∠
0
Vb = 35
∠
-120
Vc = 69
∠
+120
Ia = 4
∠
+135
Ib = 4
∠
-45
Ic = 0
BC
Va = 69
∠
0
Vb = 35
∠
-120
Vc = 35
∠
+120
Ia = 0
Ib = 4
∠
+15
Ic = 4
∠
-165