I.L. 40-201.9
Power Automation and Protection Division
I-10
REL 352 Version 1.00
The apparent impedances seen by the relay in each of the above positions and the expected operation of the
inner (21 BI) and outer (21 BO) blinders are the following:
The following tests make sure that the transmitter and receiver are connected in the unit.
NOTE:
Make sure that the loopback connections described in 7.1 and 7.2 are made.
Also, the metered value CHRX displayed should be ARM.
Test #1 indicates the sequence of positions in the RX diagram to be applied and the time in cycles to hold the
position and the action of the relay.
The fault impedance measured should be 10.6
∠
105 ohms.
POS
Z app
21 BI
41 BO
1
13.8
∠
5
No
No
2
4.47
∠
25
No
Yes
3
3.33
∠
65
Yes
Yes
4
5.00
∠
100
No
Yes
5
10.6
∠
105
No
No
TEST #1
Trip OST on the Way Out
Pos
Time
Trip Action
A
1
2
3
4
5
60
5
20
5
60
50-67 ms after 2